B&R Industrial Automation (a Business Unit of ABB) X20BC008T
X20BC008T: Communication technology: OPC UA Field eXchange (FX); I/O configuration via OPC UA FX; 400 µs minimum cycle time; Integrated switch for daisy-chaining; 2x 1 Gbit/s full-duplex mode; OPC UA diagnostics and module diagnostics at runtime via OPC UA clients; This bus controller provides OPC UA FX functions. This allows any OPC UA clients access to read or write data from I/O modules connected to the bus controller.
Технические характеристики
| Bus controller | OPC UA FX |
|---|---|
| B&R ID code | 0xF629 |
| Status indicators | Module status, bus function |
| Module status | Yes, using LED status indicator and software |
| Bus function | Yes, using LED status indicator and software |
| Bus | 3.5 W |
| Additional power dissipation caused by actuators (resistive) [W] | - |
| CE | Yes |
| UKCA | Yes |
| EAC | Yes |
| Fieldbus | 400 µs |
| Variant | 2x shielded RJ45 (switch) |
| Line length | Max. 100 m between 2 stations (segment length) |
| Transfer rate | 1 Gbit/s |
| Physical layer | 100BASE-TX/1000BASE-T |
| Half-duplex | No |
| Full-duplex | Yes |
| Autonegotiation | Yes |
| Auto-MDI/MDIX | Yes |
| X2X Link | 400 µs |
| Synchronization between bus systems possible | Yes |
| Electrical isolation | OPC UA FX isolated from bus and I/O |
| Horizontal | Yes |
| Vertical | Yes |
| 0 to 2000 m | No limitation |
| >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP20 |
| Horizontal mounting orientation | -25 to 45°C |
| Vertical mounting orientation | -25 to 40°C |
| Derating | See section "Derating". |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
| Operation | 5 to 95%, non-condensing |
| Note | Order 1x terminal block X20TB12 separately.Order 1x power supply module X20PS9400 or X20PS9402 separately.Order 1x bus base X20BB80X separately. |
| Pitch | 37.5+0.2mm |