X20cAO4632: 4 analog outputs; Either current or voltage signal possible; 16-bit digital converter resolution; The module is equipped with 4 outputs with 16-bit (including sign) digital converter resolution. It is possible to select between the current and voltage signal using different terminals.
Технические характеристики
| I/O module | 4 analog outputs ±10 V or 0 to 20 mA |
|---|---|
| B&R ID code | 0xD575 |
| Status indicators | I/O function per channel, operating state, module status |
| Module run/error | Yes, using status LED and software |
| Channel type | Yes, using software |
| Bus | 0.01 W |
| Internal I/O | 1.8 W |
| Additional power dissipation caused by actuators (resistive) [W] | - |
| CE | Yes |
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 GcIP20, Ta (see X20 user's manual)FTZÚ 09 ATEX 0083X |
| UL | cULus E115267Industrial control equipment |
| HazLoc | cCSAus 244665Process control equipmentfor hazardous locationsClass I, Division 2, Groups ABCD, T5 |
| DNV GL | Temperature:B(0 - 55°C)Humidity:B(up to 100%)Vibration:B(4 g)EMC:B(bridge and open deck) |
| LR | ENV1 |
| KR | Yes |
| ABS | Yes |
| EAC | Yes |
| Output | ±10 V or 0 to 20 mA, via different terminal connections |
| Напряжение питания | Max. 0.11%, from 10 MΩ → 1 kΩ, resistive |
| Current | Max. 0.5%, from 1 Ω → 600 Ω, resistive |
| Conversion time | 50 µs for all outputs |
| Settling time on output change over entire range | 500 µs |
| Switch on/off behavior | Internal enable relay for booting |
| Gain | 0.09% |
| Offset | 0.045% |
| Output protection | Short circuit protection |
| Short-circuit proof | Current limiting ±40 mA |
| Output filter | 1st-order low pass / cutoff frequency 10 kHz |
| Nonlinearity | <0.005% |
| Напряжение питания | 500 Veff |
| Electrical isolation | Channel isolated from busChannel not isolated from channel |
| Horizontal | Yes |
| Vertical | Yes |
| 0 to 2000 m | No limitations |
| >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP20 |
| Horizontal mounting orientation | -25 to 60°C |
| Vertical mounting orientation | -25 to 50°C |
| Derating | See section "Derating" |
| Starting temperature | Yes, -40°C |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
| Operation | Up to 100%, condensing |
| Note | Order 1x X20TB12 terminal block separatelyOrder 1x X20cBM11 bus module separately |
| Pitch | 12.5+0.2mm |