X20cBC0087: Fieldbus: Modbus/TCP, Modbus/UDP; I/O configuration via the fieldbus; DHCP-capable; Bootp-capable; Integrated double switch for efficient cabling; Configurable I/O cycle (0.5 to 4 ms); Response time: <1 - 8 ms (depending on the load on the integrated switch); Validity check for command sequences before execution; Established in 1979, the Modbus protocol has approved the use of Ethernet with both Modbus TCP and Modbus/UDP. Today, Modbus TCP is an open Internet draft standard introduced by Schneider Automation to the Internet Engineering Task Force (IETF), the organization responsible for Internet standardization. The Modbus services and object model have been preserved since the original version and left unchanged for use with the TCP/IP transmission medium.; Modbus/UDP differs from Modbus TCP in that it uses connectionless communication via UDP/IP. The advantages of faster and easier communication with UDP/IP also brings with it the disadvantage of requiring error detection and correction in the application layer.; This bus controller makes it possible to connect X2X Link I/O nodes to Modbus via Ethernet. The bus controller can be operated on B&R controllers through the use of Automation Studio or on third-party systems with Modbus TCP or -UDP master functionality.; Only the standard function model (see the respective module description) is supported when the bus controller is used together with multi-function modules it has automatically configured itself.; All other function models are supported when configured accordingly in Automation Studio V4.3 or later.; Automation Studio can be downloaded at no cost from the B&R websitewww.br-automation.com. The evaluation license is permitted to be used to create complete configurations for fieldbus bus controllers at no cost.
Технические характеристики
| Bus controller | Modbus TCP/UDP slave |
|---|---|
| B&R ID code | 0xD577 |
| Status indicators | Module status, bus function |
| Module status | Yes, using status LED and software |
| Bus function | Yes, using status LED and software |
| Bus | 2 W |
| Additional power dissipation caused by actuators (resistive) [W] | - |
| CE | Yes |
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 GcIP20, Ta (see X20 user's manual)FTZÚ 09 ATEX 0083X |
| UL | cULus E115267Industrial control equipment |
| HazLoc | cCSAus 244665Process control equipmentfor hazardous locationsClass I, Division 2, Groups ABCD, T5 |
| DNV GL | Temperature:B(0 - 55°C)Humidity:B(up to 100%)Vibration:B(4 g)EMC:B(bridge and open deck) |
| LR | ENV1 |
| KR | Yes |
| EAC | Yes |
| Fieldbus | 1 ms |
| Variant | 2x shielded RJ45 (switch) |
| Line length | Max. 100 m between 2 stations (segment length) |
| Transfer rate | 10/100 Mbit/s |
| Physical layer | 10BASE-T/100BASE-TX |
| Half-duplex | Yes |
| Full-duplex | Yes |
| Autonegotiation | Yes |
| Auto-MDI/MDIX | Yes |
| X2X Link | 500 μs |
| Synchronization between bus systems possible | No |
| Electrical isolation | Modbus isolated from bus and I/O |
| Horizontal | Yes |
| Vertical | Yes |
| 0 to 2000 m | No limitation |
| >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP20 |
| Horizontal mounting orientation | -25 to 60°C |
| Vertical mounting orientation | -25 to 50°C |
| Derating | - |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
| Operation | Up to 100%, condensing |
| Note | Order 1x X20TB12 terminal block separatelyOrder 1x X20cPS9400 power supply module separatelyOrder 1x X20cBB80 bus base separately |
| Spacing | 37.5+0.2mm |