B&R Industrial Automation (a Business Unit of ABB) X20CIF10E3-1
X20cIF10E3-1: PROFINET IO device; Integrated switch for efficient cabling; The interface module is equipped with a PROFINET IO device interface. This allows the B&R system (I/O modules, POWERLINK, etc.) to be connected to systems from other manufacturers and makes it possible to quickly and easily transfer data in both directions.; The interface module can be operated in X20 CPUs or in the expandable POWERLINK bus controller X20BC1083.; The interface is equipped with 2 RJ45 connections. Both connections result in an integrated switch. This makes it easy to implement daisy chain cabling.
Технические характеристики
| Communication module | PROFINET IO device (slave) |
|---|---|
| B&R ID code | 0xE238 |
| Status indicators | Module status, network status, data transfer |
| Module status | Yes, using status LED and software |
| Network status | Yes, using status LED and software |
| Data transfer | Yes, using status LED |
| Power consumption | 2 W |
| Additional power dissipation caused by actuators (resistive) [W] | - |
| CE | Yes |
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 GcIP20, Ta (see X20 user's manual)FTZÚ 09 ATEX 0083X |
| UL | cULus E115267Industrial control equipment |
| HazLoc | cCSAus 244665Process control equipmentfor hazardous locationsClass I, Division 2, Groups ABCD, T5 |
| DNV GL | Temperature:B(0 - 55°C)Humidity:B(up to 100%)Vibration:B(4 g)EMC:B(bridge and open deck) |
| LR | ENV1 |
| KR | Yes |
| ABS | Yes |
| EAC | Yes |
| Fieldbus | PROFINET IO device (slave) |
| Conformance class | C |
| Power output class | RT (switch supports IRT) |
| Netload class | III |
| Variant | 2x shielded RJ45 (switch) |
| Cable length | Max. 100 m between 2 stations (segment length) |
| Transfer rate | 100 Mbit/s |
| Physical layer | 100BASE-TX |
| Half-duplex | Yes |
| Full-duplex | Yes |
| Autonegotiation | Yes |
| Auto-MDI/MDIX | Yes |
| Controller | netX100 |
| Electrical isolation | PLC isolated from PROFINET IO (IF1 and IF2) |
| Horizontal | Yes |
| Vertical | Yes |
| 0 to 2000 m | No limitations |
| >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP20 |
| Horizontal mounting orientation | -25 to 60°C |
| Vertical mounting orientation | -25 to 50°C |
| Derating | - |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
| Operation | Up to 100%, condensing |
| Slot | In the X20c CPU and in the X20cBC1083 expandable bus controller |