B&R Industrial Automation (a Business Unit of ABB) X20DO4623
X20DO4623: 4 digital outputs; Outputs with integrated snubber circuit; Outputs with 100 to 240 VAC; L switching; 50 Hz or 60 Hz; 2-wire connections; Integrated full-wave control; 240 V coding; The module is a digital output module that is equipped with 4 SSR outputs with zero cross-over switches and uses 2-line connections. The module is also equipped with integrated full-wave control. The supply (L and N) is fed directly to the module.
Технические характеристики
| I/O module | 4 digital SSR outputs 100 to 240 VAC for 2-wire connections |
|---|---|
| B&R ID code | 0x267C |
| Status indicators | I/O function per channel, operating state, module status |
| Module run/error | Yes, using LED status indicator and software |
| Outputs | Yes, using LED status indicator |
| Bus | 0.52 W |
| Internal I/O | - |
| External I/O | 0.38 W |
| Additional power dissipation caused by actuators (resistive) [W] | +3.2 |
| CE | Yes |
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 GcIP20, Ta (see X20 user's manual)FTZÚ 09 ATEX 0083X |
| UL | cULus E115267Industrial control equipment |
| HazLoc | cCSAus 244665Process control equipmentfor hazardous locationsClass I, Division 2, Groups ABCD, T5 |
| EAC | Yes |
| KC | Yes |
| Variant | SSR |
| Circuit | L-switching |
| Напряжение питания | 100 to 240 VAC |
| Напряжение питания | 264 VAC |
| Rated frequency | 47 to 63 Hz |
| Nominal output current | 0.5 A |
| Total nominal current | 1 A |
| Surge current | 7 A (20 ms), 2 A (1 s) |
| Connection type | 2-wire connections |
| Zero-crossing switches | Yes |
| Leakage current | Max. 1.5 mA at 240 V |
| Напряжение питания | 1.6 V |
| 0 → 1 | ≤9.3 ms |
| 1 → 0 | ≤9.3 ms |
| Напряжение питания | Tested at 2500 VAC |
| Напряжение питания | No |
| Напряжение питания | Yes |
| Minimum | 75 VAC |
| External | Generally varistor or fuse |
| Internal | Snubber circuit (RC element) |
| Electrical isolation | Channel isolated from bus and I/O power supply |
| Horizontal | Yes |
| Vertical | Yes |
| 0 to 2000 m | No limitation |
| >2000 m | Not permitted |
| Degree of protection per EN 60529 | IP20 |
| Horizontal mounting orientation | -25 to 60°C |
| Vertical mounting orientation | -25 to 50°C |
| Derating | See section "Derating". |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
| Operation | 5 to 95%, non-condensing |
| Note | Order 1x terminal block X20TB32 separately.Order 1x bus module X20BM12 separately. |
| Pitch | 12.5+0.2mm |