B&R Industrial Automation (a Business Unit of ABB) X20DO6639
X20DO6639: 6 digital outputs; Relay module for 240 VAC / 30 VDC; Switching current 2 A; 6 normally open contacts; Single-channel isolated outputs; The module is equipped with 6 relay outputs.
Технические характеристики
| I/O module | 6 digital outputs 30 VDC / 240 VAC, outputs are single-channel isolated |
|---|---|
| B&R ID code | 0xDF50 |
| Status indicators | I/O function per channel, operating state, module status |
| Module run/error | Yes, using status LED |
| Outputs | Yes, using status LED |
| Bus | 1 W |
| Internal I/O | - |
| Additional power dissipation caused by actuators (resistive) [W] | +0.36 |
| CE | Yes |
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 GcIP20, Ta (see X20 user's manual)FTZÚ 09 ATEX 0083X |
| UL | cULus E115267Industrial control equipment |
| HazLoc | cCSAus 244665Process control equipmentfor hazardous locationsClass I, Division 2, Groups ABCD, T5 |
| DNV GL | Temperature:B(0 - 55°C)Humidity:B(up to 100%)Vibration:B(4 g)EMC:B(bridge and open deck) |
| LR | ENV1 |
| KR | Yes |
| ABS | Yes |
| EAC | Yes |
| Variant | Relay / Normally open contactChannels are single-channel isolated |
| Напряжение питания | 30 VDC / 240 VAC |
| Напряжение питания | 264 VAC |
| Напряжение питания | Max. 110 VDC / 264 VAC |
| Rated frequency | DC / 45 to 63 Hz |
| Nominal output current | 2 A at 30 VDC / 2 A at 240 VAC |
| Total nominal current | 10 A at 30 VDC / 10 A at 240 VAC |
| Actuator power supply | External |
| Contact resistance | Max. 100 mΩ |
| 0 → 1 | ≤10 ms |
| 1 → 0 | ≤10 ms |
| Channel - Bus | Tested at 2300 VAC |
| Channel - Channel | Tested at 750 VAC |
| Electrical | Min.120 x 103ops. (at 2 A / 240 VAC) |
| Mechanical | Min. 2 x 107ops. |
| Minimum | 0.05 W DC / 2.4 W AC |
| Maximum | 60 W DC / 480 W AC |
| AC | RC combination or VDR |
| DC | Inverse diode, RC combination or VDR |
| Internal | None |
| Electrical isolation | Channel isolated from bus and I/O power supply |
| Horizontal | Yes |
| Vertical | Yes |
| 0 to 2000 m | No limitations |
| >2000 m | Not permitted |
| Degree of protection per EN 60529 | IP20 |
| Horizontal mounting orientation | -25 to 60°C |
| Vertical mounting orientation | -25 to 50°C |
| Derating | - |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
| Operation | 5 to 95%, non-condensing |
| Note | Order 1x X20TB32 terminal block separately,Order 1x X20BM12 bus module separately |
| Pitch | 12.5+0.2mm |