BK1120

Beckhoff Automation GmbH & Co. KG BK1120

BK1120 EtherCAT Bus Coupler for standard Bus Terminals

Категории:

Технические характеристики

Number of Bus Terminals64 (255 with K-bus extension)
Max. number of bytes fieldbus1024 byte input and 1024 byte output
Configurationvia KS2000 or EtherCAT (ADS)
Transmission rate100 Mbit/s
Bus interface2 x RJ45
Transmission mediumEthernet/EtherCAT Cat.5 cable
Power supply24 V DC (-15%/+20%)
Input current70 mA + (total K-bus current)/4, 500 mA max.
Starting currentapprox. 2.5 x continuous current
Recommended fuse≤ 10 A
Current supply K-bus1750 mA
Power contactsmax. 24 V DC/max. 10 A
Electrical isolation500 V (power contact/supply voltage/Ethernet)
Distance between stations100 m (100BASE-TX)
Data transfer time0.01 ms in the case of 10 modules for 32 bit inputs and outputs each (without K-bus run-time)
Массаapprox. 150 g
Operating temperature-25…+60°C
Storage temperature-40…+85°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP20/variable
Approvals/markingsCE, CCC, UL, ATEX, IECEx, cFMus
Ex markingATEX: II 3G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc cFMus: Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx ec IIC T4 Gc
DescriptionThe BK1120 EtherCAT Coupler is the link between the EtherCAT protocol at fieldbus level and the Bus Terminals. The coupler converts the passing telegrams from Ethernet 100BASE-TX to the internal, fieldbus-independent terminal bus. A station consists of a