Beckhoff Automation GmbH & Co. KG EK1300
EK1300 EtherCAT P coupler
Категории:
Технические характеристики
| Task within EtherCAT system | coupling of EtherCAT Terminals (ELxxxx) to 100BASE-TX EtherCATÂ P networks |
|---|---|
| Transmission medium | EtherCATÂ P cable, shielded, to 100BASE-TX EtherCATÂ P networks |
| Bus interface | 2 x M8 socket, P-coded, shielded |
| Power supply | from EtherCATÂ P (24Â VÂ DC (-15%/+20%) for U S and U P ) |
| Sum current | from EtherCATÂ P, max. 3Â A per U S and U P |
| Current consumption from US | 40 mA + (â E-bus current/4) |
| Current consumption from UP | typ. 4 mA |
| Current supply E-bus | 2000 mA |
| Current rating per port | max. 3Â A per U S and U P |
| Electrical isolation | 500 V (power contact/supply voltage/Ethernet) |
| Operating temperature | -25â¦+55°C |
| Storage temperature | -40â¦+85°C |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE, UL |
| Description | The EK1300 EtherCATÂ P coupler integrates the EtherCAT Terminals into the EtherCATÂ P network. The coupler converts the passing telegrams from Ethernet 100BASE-TX to E-bus signal representation. A station consists of a coupler and any number of EtherCAT |