Task within EtherCAT systemcoupling of EtherCAT Terminals (ELxxxx) to 100BASE-TX EtherCAT networks
Transmission mediumEthernet/EtherCAT cable (min. Cat.5), shielded
Distance between stationsmax. 100 m (100BASE-TX)
Number of EtherCAT Terminalsup to 65,534
ProtocolEtherCAT
Propagation delayapprox. 1 µs
Transmission rate100 Mbit/s
Bus interface2 x RJ45
Напряжение питания24 V DC (-15%/+20%)
Current supply E-bus1000 mA
Current consumption from UP40 mA + load
Current consumption from US100 mA + (∑ E-bus current/4)
Number of inputs8
SpecificationEN 61131-2, type 1/3
Напряжение питания-3…+5 V (EN 61131-2, type 1/3)
Напряжение питания11…30 V (EN 61131-2, type 3)
Input filtertyp. 3 ms
Input currenttyp. 3 mA (EN 61131-2, type 3)
Number of outputs4
Load typeresistive, inductive, lamp load
Max. output current0.5 A (short-circuit proof) per channel
Short-circuit currenttyp. < 2 A
Reverse polarity protectionyes
Switching-off energy< 150 mJ/channel
Switching timestyp. T ON : 60 µs, typ. T OFF : 300 µs
Electrical isolation500 V (power contact/supply voltage/Ethernet), 500 V (E-bus/field potential)
Operating temperature-25…+60°C
Storage temperature-40…+85°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP20/variable
Approvals/markingsCE, UL
DescriptionThe EK1818 EtherCAT Coupler is the link between the EtherCAT protocol at fieldbus level and the EtherCAT Terminals. In addition, eight digital inputs and four digital outputs are integrated. The resulting design is particularly suitable for applications