Beckhoff Automation GmbH & Co. KG EL2014
EL2014 EtherCAT Terminal, 4-channel digital output, 24 V DC, 0.5 A, with extended diagnostics
Категории:
Технические характеристики
| Connection technology | 2-wire |
|---|---|
| Number of outputs | 4 |
| Напряжение питания | 24 V DC (-15%/+20%) |
| Load type | resistive, inductive, lamp load |
| Distributed clocks | â |
| Max. output current | 0.5 A (short-circuit proof) per channel |
| Short-circuit current | typ. < 1 A |
| Reverse polarity protection | yes |
| Switching-off energy | < 150 mJ/channel |
| Switching times | typ. T ON : 50 µs, typ. T OFF : 100 µs |
| Current consumption E-bus | typ. 60 mA |
| Current consumption power contacts | typ. 15 mA + load |
| Bit width in the process image | 4 bit output, 20 bit diagnositcs |
| Configuration | via TwinCAT System Manager |
| Electrical isolation | 500 V (E-bus/field potential) |
| Special features | diagnostics via process data and LED: overtemperature, PowerFail, short circuit (per channel) |
| Масса | approx. 70 g |
| Operating temperature | -25â¦+60°C |
| Storage temperature | -40â¦+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Pluggable wiring level | for all ESxxxx terminals |
| Approvals/markings | CE, CCC, ATEX, IECEx, cFMus |
| Ex marking | ATEX: II 3G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc cFMus: Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx ec IIC T4 Gc |
| Description | The EL2014 digital output terminal connects the binary 24 V DC control signals from the automation device on to the actuators at the process level with electrical isolation. The EtherCAT Terminal contains four channels that indicate its signal state by |