Beckhoff Automation GmbH & Co. KG EL2602
EL2602 EtherCAT Terminal, 2-channel relay output, 230 V AC, 30 V DC, 5 A
Категории:
Технические характеристики
| Connection technology | relay output |
|---|---|
| Number of outputs | 2 x make contacts for power contact |
| Напряжение питания | 230 V AC/30 V DC |
| Load type | resistive, inductive, lamp load |
| Distributed clocks | â |
| Resistive switching current | 5 A AC/DC per channel |
| Minimum permitted load | 10 mA at 5 V DC |
| Inductive switching current | 2 A AC/DC per channel |
| Lamp test, electronic ballast | 4 x 58 W |
| Current consumption E-bus | typ. 170 mA |
| Current consumption power contacts | load-dependent |
| Bit width in the process image | 2 outputs |
| Operating cycles mech. (min.) | 2 x 10 7 |
| Operating cycles electr. (min.) | 1 x 10 5 (5Â A/30Â VÂ DC) |
| Configuration | no address or configuration setting |
| Electrical isolation | 500 V (E-bus/field potential) |
| Special features | 1-wire connection possible |
| Масса | approx. 50 g |
| Operating temperature | -25â¦+55°C |
| Storage temperature | -40â¦+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Pluggable wiring level | for all ESxxxx terminals |
| Approvals/markings | CE, UL |
| Description | The EL2602 output terminal has two relays each of which has a single contact. The relay contact is connected to the power contacts, which are suitable for use at up to 230Â VÂ AC, and can be generally used for switching devices requiring mains power. The |