EL2622

Beckhoff Automation GmbH & Co. KG EL2622

EL2622 EtherCAT Terminal, 2-channel relay output, 230 V AC, 30 V DC, 5 A, without power contacts

Категории:

Технические характеристики

Connection technologyrelay output
Number of outputs2 x make contacts
Напряжение питания230 V AC/30 V DC
Load typeresistive, inductive, lamp load
Distributed clocks–
Resistive switching current5 A AC/DC per channel
Minimum permitted load10 mA at 5 V DC
Inductive switching current2 A AC/DC per channel
Lamp test, electronic ballast4 x 58 W
Current consumption E-bustyp. 170 mA
Current consumption power contacts–
Bit width in the process image2 outputs
Operating cycles mech. (min.)2 x 10 7
Operating cycles electr. (min.)1 x 10 5 (5 A/30 V DC)
Configurationno address or configuration setting
Electrical isolation500 V (E-bus/field potential)
Special features–
Массаapprox. 50 g
Operating temperature-25…+55°C
Storage temperature-40…+85°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP20/variable
Pluggable wiring levelfor all ESxxxx terminals
Approvals/markingsCE, UL
DescriptionThe EL2622 output terminal has two relays, each with a single contact. It is universally applicable for switching mains voltage consumers. The signal state of the EtherCAT Terminal is indicated by light emitting diodes. The EL2622 features potential-free
Получить предложение по этой позиции