Beckhoff Automation GmbH & Co. KG EL2642
EL2642 EtherCAT Terminal, 2-channel reed output, multiplexer, 48 V AC/DC, 0.5 A, potential-free, 1 x 4
Категории:
Технические характеристики
| Technology | multiplexer |
|---|---|
| Connection technology | 2-wire reed output |
| Connection type | direct plug-in technology/push-in |
| Number of outputs | 2 x multiplexer 1 on 4 |
| Напряжение питания | 48 V AC/DC |
| Load type | resistive |
| Distributed clocks | â |
| Resistive switching current | 0.5 A AC/DC per channel (max. sum current 1Â A under UL conditions, otherwise 2 A) |
| Inductive switching current | no data |
| Switching capacity | max. 10Â W |
| Continuous power | max. 10Â W |
| Current consumption E-bus | typ. 60 mA |
| Electrical isolation | 500 V (E-bus/field potential) |
| Current consumption power contacts | typ. 20 mA |
| Configuration | no address or configuration setting |
| On-resistance | typ. 0.2 Ω |
| Switching on speed | typ. 1 ms, max. 5 ms |
| Switching off speed | typ. 1 ms, max. 5 ms |
| Напряжение питания | 170 V |
| Short-circuit current | not short-circuit proof, see peak current |
| Peak current | 1 A (100Â ms) |
| Thermal dissipation | typ. 1Â W |
| Special features | fast reed relays, temperature measurement |
| Масса | approx. 100 g |
| Operating temperature | -25â¦+55°C |
| Storage temperature | -40â¦+85°C |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE |
| Description | With the switching terminals of the EL/ELM264x (reed) and ELM274x (solid-state) series, Beckhoff significantly expands the application possibilities of the integrated measurement technology of the ELM3xxx series, as well as normal EL3xxx/EL4xxx analog |