EL2712

Beckhoff Automation GmbH & Co. KG EL2712

EL2712 EtherCAT Terminal, 2-channel TRIAC output, 12…230 V AC, 0.5 A

Категории:

Технические характеристики

Connection technologyTRIAC output, 2-wire
Number of outputs2 x make contacts
Напряжение питания12…230 V AC
Load typeresistive, inductive
Distributed clocks–
Max. output current0.5 A per channel
Switching timesin zero crossing, 0.1…10 ms
Rotating field frequency47…63 Hz
Напряжение питания> 275 V
Peak current40 A (16 ms), 1.5 A (30 s)
Standby current0.6 mA
Leakage current (OFF state)typ. 0.8 mA, max. 1.5 mA
Switch-on time0.1…10 ms, zero crossing
Switch-off timeT/2
Напряжение питанияmax. 1.5 V (60 mA…1 A), 150 Ω (< 60 mA)
Current consumption E-bustyp. 120 mA
Current consumption power contacts–
Bit width in the process image2 outputs
Configurationno address or configuration setting
Electrical isolation500 V (E-bus/field voltage), 3750 V AC (1 min.)
Special featuressuitable for conventional blind motors
Массаapprox. 55 g
Operating temperature0…55°C
Storage temperature-25…+85°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP20/variable
Pluggable wiring levelfor all ESxxxx terminals
Approvals/markingsCE
DescriptionThe EL2712 output terminal uses a power switch to control mains voltage from 12 V to 230 V AC. The switching element is a TRIAC, which is connected to the power contact potential. As a semiconductor switch, it is not subject to wear. The steady load