EL3201

Beckhoff Automation GmbH & Co. KG EL3201

EL3201 EtherCAT Terminal, 1-channel analog input, temperature, RTD (Pt100), 16 bit

Категории:

Технические характеристики

Number of inputs1
Power supplyvia the E-bus
Distributed clocks–
Input filter cut-off frequencytyp. 1 kHz
Sensor typePt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, resistance measurement (e.g. potentiometer, 10 Ω…4 kΩ), KTY sensors (types see documentation)
Connection technology2-, 3-, 4-wire (default: 2-wire)
Conversion timeapprox. 24 ms default setting, 4…500 ms configurable
Measuring current< 0.5 mA (load-dependent)
Temperature range-200…+850°C (Pt sensors); -60…+250°C (Ni sensors)
Resolution0.1°C per digit
Measurement error/uncertainty< ±0.5°C for Pt sensors
Electrical isolation500 V (E-bus/signal voltage)
Current consumption E-bustyp. 190 mA
Current consumption power contacts–
Bit width in the process image1 x 32 bit RTD input
Special featuresintegrated digital filter, limit value monitoring, variable connection technology
Массаapprox. 60 g
Operating temperature-25…+60°C
Storage temperature-40…+85°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Pluggable wiring levelfor all ESxxxx terminals
Protect. rating/installation pos.IP20/variable
Approvals/markingsCE, CCC, UL, ATEX, IECEx, cFMus
Ex markingATEX: II 3G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc cFMus: Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx ec IIC T4 Gc
DescriptionThe EL3201 analog input terminal facilitates the direct connection of a resistance sensor. The measured resistance value can either be output directly in ohms or transformed into a temperature. If the temperature at the measuring point is of interest
Получить предложение по этой позиции