EL3356

Beckhoff Automation GmbH & Co. KG EL3356

EL3356 EtherCAT Terminal, 1-channel analog input, measuring bridge, full bridge, 16 bit

Категории:

Технические характеристики

Number of inputs2, for 1 resistor bridge in full bridge technology
Power supplyvia the E-bus
Distributed clocks–
Measuring range UDmax. ±27 mV
Measuring range UREFmax. ±13.8 V
Internal resistance> 200 kΩ (U REF ), > 1 MΩ (U D )
Supported nominal sensitivityall, parameter resolution: 0.01 µV/V; recommended: 0.5…4 mV/V
Input filter cut-off frequency10 kHz low pass (-3 dB)
Conversion rate100…4 samples/s (10…250 ms conversion time)
Power supply UVup to 12 V DC from power contacts, dependent on sensor
Resolution16 bit, 32 bit presentation
Measurement error/uncertainty< ±0.01% for the calculated load value in relation to the final load value with a 12 V feed and 24 mV bridge voltage (hence nominal strain gauge characteristic value of 2 mV/V), self-calibration active, 50 Hz filter active
Current consumption E-bustyp. 210 mA
Current consumption power contactsdependent on strain gauge supply, min. 1 mA
Special featuresself-calibration, quadruple averager, dynamic filters
Массаapprox. 60 g
Operating temperature-25…+55°C
Storage temperature-40…+85°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Pluggable wiring levelfor all ESxxxx terminals
Protect. rating/installation pos.IP20/variable
Approvals/markingsCE, CCC, UL, ATEX, IECEx, cFMus
Ex markingATEX: II 3G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc cFMus: Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx ec IIC T4 Gc
DescriptionThe analog EL3356 input terminal enables direct connection of a resistor bridge or load cell in a 4- or 6-wire connection technology. The ratio between the bridge voltage UD and the supply voltage UREF is determined simultaneously in the input circuit