EL3403

Beckhoff Automation GmbH & Co. KG EL3403

EL3403 EtherCAT Terminal, 3-channel analog input, power measurement, 500 V AC, 1 A, 16 bit

Категории:

Технические характеристики

Number of inputs3 x current, 3 x voltage
Oversampling factor–
Distributed clocks–
Conversion timemains-synchronous
Measured valuescurrent (I1, I2, I3), voltage, effective power, reactive power, apparent power, energy, cos φ, frequency
Напряжение питанияmax. 500 V AC 3~ (UL X -N: max. 288 V AC)
Measuring currentmax. 1 A (AC), via measuring transformers x A/1 A
Resolution1 µA, 0.1 mV, 10 mW
Measurement error/uncertainty0.5% relative to full scale value (U/I), 1% calculated value
Measuring proceduretrue RMS
Update timenet-synchronous
Electrical isolation1500 V
Current consumption E-bustyp. 120 mA
Current consumption power contacts–
Bit width in the process image62 byte PM input, 3 byte PM output
Special featurestrue RMS value calculation, optional single-phase operation
Массаapprox. 75 g
Storage temperature-40…+85°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Pluggable wiring levelfor all ESxxxx terminals
Protect. rating/installation pos.IP20/variable
Approvals/markingsCE, UL
DescriptionThe EL3403 EtherCAT Terminal enables the measurement of all relevant electrical data of the supply network. The voltage is measured via the direct connection of L1, L2, L3 and N. The current of the three phases L1, L2 and L3 is fed via simple current
Получить предложение по этой позиции