EL3423

Beckhoff Automation GmbH & Co. KG EL3423

EL3423 EtherCAT Terminal, 3-channel analog input, power measurement, 480 V AC/DC, 1 A, 24 bit

Категории:

Технические характеристики

Number of inputs3 x current, 3 x voltage
Oversampling factor–
Distributed clocks–
Update interval> 10 s
Measured valuesenergy, power, power quality factor
Напряжение питанияmax. 480 V AC 3~ (UL X -N: max. 277 V AC/240 V DC)
Measuring currentmax. 1 A (AC/DC), via measuring transformers x A/1 A
Measurement error/uncertainty0.5% relative to full scale value (U/I), 1% calculated value
Update timenet-synchronous
Monitoring functionphase order, phase failure, phase asymmetry, undervoltage/overvoltage (adjustable)
Electrical isolation2500 V
Current consumption E-bustyp. 120 mA
Current consumption power contacts–
Special featuresmains monitoring, optional single-phase operation
Массаapprox. 75 g
Operating temperature-25…+60°C
Storage temperature-40…+85°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Approvals/markingsCE, UL
DescriptionThe EL3423 EtherCAT Terminal enables the measurement of relevant data for an efficient energy management system. The voltage is measured internally via direct connection of L1, L2, L3 and N. The current of the three phases L1, L2 and L3 is fed via simple
Получить предложение по этой позиции