Beckhoff Automation GmbH & Co. KG EL3632
EL3632 EtherCAT Terminal, 2-channel analog input, IEPE/accelerometer, 16 bit, 50 ksps
Категории:
Технические характеристики
| Number of inputs | 2 |
|---|---|
| Напряжение питания | IEPE constant current supply and recording of modulated AC voltage |
| Distributed clocks | yes |
| Input filter cut-off frequency | analog parameterizable 5 th order low-pass filter up to 25 kHz, typically 0.05 Hz high-pass filter |
| Conversion time | 20 μs (max. 50 ksamples/s) |
| Measuring range | default ±5 V up to 25 kHz, ±250 mV up to 10 Hz |
| Power supply UV | 24 V DC via power contacts |
| Напряжение питания | max. power contact voltage less 1 V |
| Sensor state monitoring | yes, through monitoring of the bias voltage |
| Supply current IEXCITE | typ. 2/4/8 mA (separately configurable for both channels) |
| Resolution | 16 bit (incl. sign) |
| Measurement error/uncertainty | < ±0.5% (DC; relative to full scale value) |
| Current consumption E-bus | typ. 220 mA |
| Current consumption power contacts | 24 V, typ. 20 mA + load |
| Special features | automatic anti-aliasing function, wire breakage detection |
| Масса | approx. 60 g |
| Operating temperature | -25â¦+55°C |
| Storage temperature | -40â¦+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/see documentation |
| Approvals/markings | CE, CCC, UL, ATEX, IECEx, cFMus |
| Ex marking | ATEX: II 3G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc cFMus: Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx ec IIC T4 Gc |
| Description | Accelerometers with IEPE interface can be directly connected to the EL3632 EtherCAT Terminal. The measuring signals are analyzed on the PC via the TwinCAT library. This enables all benefits of the PC platform, such as performance and flexibility, to be |