ELX1054

Beckhoff Automation GmbH & Co. KG ELX1054

ELX1054 EtherCAT Terminal, 4-channel digital input, NAMUR, Ex i

Категории:

Технические характеристики

Technologydigital input
SpecificationNAMUR (IEC 60947-5-6)
Number of inputs4
Connection technology2-wire
Напряжение питанияtyp. 8.2 V DC
Signal current “0”≤ 1.2 mA
Signal current “1”≥ 2.1 mA
Switching hysteresistyp. 200 µA
Short-circuit currenttyp. 7 mA
Fault detectionI ≤ 200 µA (cable break), I ≥ 6.3 mA (short circuit)
Max. switching frequencytyp. 5 kHz (duty cycle 50%)
Напряжение питания24 V DC (via power contacts), ELX9560 power supply
Current consumption power contactstyp. 15 mA + load
Current consumption E-bustyp. 70 mA
Массаapprox. 55 g
Operating temperature-25…+60°C
Storage temperature-40…+85°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP20/see documentation
Approvals/markingsCE, UL, ATEX, IECEx, cFMus, CCC
Ex markingATEX:   II 3(1)G Ex ec [ia Ga] IIC T4 Gc   II (1)D [Ex ia Da] IIIC   I (M1) [Ex ia Ma] I IECEx:   Ex ec [ia Ga] IIC T4 Gc   [Ex ia Da] IIIC   [Ex ia Ma] I cFMus:   AIS Class I, II, III, Division 1, Groups A thru G   Class I, Division 2, Groups A, B, C, D   Class I, Zone 2, AEx ec [ia Ga] IIC T4 Gc   [AEx ia Da] IIIC T4
DescriptionThe ELX1054 digital input terminal acquires signals from NAMUR field devices according to EN 60947-5-6. The sensors are supplied with a voltage of 8.2 V and return a diagnosable current signal. In this way, a wire breakage or short-circuit can be