Beckhoff Automation GmbH & Co. KG ELX2002
ELX2002 EtherCAT Terminal, 2-channel digital output, 24 V DC, 45 mA, Ex i
Категории:
Технические характеристики
| Technology | current output |
|---|---|
| Connection technology | 2-wire |
| Number of outputs | 2 |
| Напряжение питания | 24 V DC |
| Напряжение питания | load-dependent (R i = 254 Ω) |
| Load type | resistive, inductive, capacitive |
| Напряжение питания | 24 V DC (via power contacts), ELX9560 power supply |
| Current consumption power contacts | typ. 10 mA + load |
| Max. output current | 45 mA per channel, â 80 mA |
| Current consumption E-bus | typ. 45 mA |
| Масса | approx. 55 g |
| Operating temperature | -25â¦+60°C |
| Storage temperature | -40â¦+85°C |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| Protect. rating/installation pos. | IP20/see documentation |
| Approvals/markings | CE, UL, ATEX, IECEx, cFMus, CCC |
| Ex marking | ATEX:   II 3(1)G Ex ec [ia Ga] IIC T4 Gc   II (1)D [Ex ia Da] IIIC   I (M1) [Ex ia Ma] I IECEx:   Ex ec [ia Ga] IIC T4 Gc   [Ex ia Da] IIIC   [Ex ia Ma] I cFMus:   AIS Class I, II, III, Division 1, Groups A thru G   Class I, Division 2, Groups A, B, C, D  Class I, Zone 2, AEx ec [ia Ga] IIC T4 Gc   [AEx ia Da] IIIC T4 |
| Description | The ELX2002 digital output terminal enables the direct connection of intrinsically safe actuators located in hazardous areas classified zone 0/20 or 1/21. The ELX2002 supplies an output voltage of 24 V DC and a maximum output current of 45 mA per |