ebm-papst Mulfingen GmbH & Co. KG W3G630-CG98-80
EC axial fan - HyBlade
Категории:
Технические характеристики
| Масса | 25,2 kg |
|---|---|
| Motor size | 112 |
| Size | 630 mm |
| Rotor surface | Painted black |
| Материал | PP plastic |
| Материал | Die-cast aluminum, painted black |
| Материал | Press-fitted, painted sheet steel blank, sprayed with PP plastic |
| Материал | Sheet steel, galvanized and coated with white aluminum plastic (RAL 9006) |
| Материал | Steel, coated with white-aluminum plastic (RAL 9006) |
| Number of blades | 5 |
| Airflow direction | A |
| Direction of rotation | Clockwise, viewed toward rotor |
| Degree of protection | IP55 |
| Insulation class | "F" |
| Рабочая температура | Occasional start-up at temperatures between -40°C and -25°C is permitted. For continuous operation at ambient temperatures below -25°C (such as refrigeration applications), use must be made of a fan design with special low-temperature bearings. |
| Moisture (F) / Environmental (H) protection class | H2+T |
| Max. permitted ambient temp. for motor (transport/storage) | +80 °C |
| Min. permitted ambient temp. for motor (transport/storage) | -40 °C |
| Installation position | Shaft horizontal or rotor on top |
| Condensation drainage holes | None |
| Mode | S1 |
| Motor bearing | Ball bearing |
| Technical features | - Output 10 VDC, max. 10 mA - Operation and alarm display - Alarm relay - Integrated PID controller - Power limiter - Motor current limitation - PFC, passive - RS-485 MODBUS-RTU - Soft start - EEPROM write cycles: 100,000 maximum - Control input 0-10 VDC / PWM - Control interface with SELV potential safely disconnected from the mains - Temperature derating - Thermal overload protection for electronics/motor - Line undervoltage / phase failure detection |
| EMC immunity to interference | According to EN 61000-6-2 (industrial environment) |
| EMC circuit feedback | According to EN 61000-3-2/3 |
| EMC interference emission | According to EN 61000-6-3 (household environment) |
| Touch current according to IEC 60990 (measuring circuit Fig. 4, TN system) | <= 3,5 mA |
| Electrical hookup | Terminal box |
| Motor protection | Thermal switch auto reset, internally connected |
| Protection class assignment | I; If a protective earth is connected.|The built-in component has several local protection class assignments.|The final protection class is determined by the intended installation. |
| Conformity with standards | EN 61800-5-1 / CE |
| Approval | UL 1004-7 + 60730-1 / EAC / CSA C22.2 No. 77 + CAN/CSA-E60730-1 |
| Comment | Conformity with standard EN 60335-1 on request |
| Phase | 3~ |
| Напряжение питания | AC |
| Напряжение питания | 400 V |
| Напряжение питания | 380 .. 480 V |
| Frequency | 50/60 Hz |
| Type of data definition | running at free air |
| Speed | 1160 min-1 |
| Power input | 730 W |
| Current draw | 1,15 A |
| Max. back pressure | 180 Pa |
| Рабочая температура | 60 °C |