ebm-papst Mulfingen GmbH & Co. KG W4D500-CM01-80
AC axial fan - HyBlade
Категории:
Технические характеристики
| Масса | 13,8 kg |
|---|---|
| Motor size | 110 |
| Size | 500 mm |
| Rotor surface | Painted black |
| Материал | Die-cast aluminum, painted black |
| Материал | Press-fitted, painted sheet steel blank, sprayed with PP plastic |
| Материал | Sheet steel, galvanized and coated with white aluminum plastic (RAL 9006) |
| Материал | Steel, coated with white-aluminum plastic (RAL 9006) |
| Number of blades | 5 |
| Airflow direction | A |
| Direction of rotation | Clockwise, viewed toward rotor |
| Degree of protection | IP54 |
| Insulation class | "F" |
| Moisture (F) / Environmental (H) protection class | H2+T |
| Max. permitted ambient temp. for motor (transport/storage) | + 80 °C |
| Min. permitted ambient temp. for motor (transport/storage) | - 40 °C |
| Installation position | Shaft horizontal or rotor on top; rotor on bottom on request |
| Condensation drainage holes | On stator side |
| Mode | S1 |
| Motor bearing | Ball bearing |
| Touch current according to IEC 60990 (measuring circuit Fig. 4, TN system) | <= 3,5 mA |
| Electrical hookup | Terminal box |
| Motor protection | Thermal switch auto reset, lead out, with basic insulation |
| Protection class assignment | I; If a protective earth is connected.|The built-in component has several local protection class assignments.|The final protection class is determined by the intended installation. |
| Conformity with standards | EN 61800-5-1 / CE |
| Approval | CSA C22.2 No. 100 / EAC / UL 1004-1 / VDE |
| Phase | 3~ / 3~ / 3~ / 3~ |
| Напряжение питания | AC / AC / AC / AC |
| Напряжение питания | 230 / 277 / 400 / 480 V |
| Connection | D / D / Y / Y |
| Frequency | 50 / 60 / 50 / 60 Hz |
| Type of data definition | running at free air / running at free air / running at free air / running at free air |
| Valid for approval / standard | CE / CE / CE / CE |
| Speed | 1400 / 1650 / 1400 / 1650 min-1 |
| Power input | 530 / 870 / 530 / 870 W |
| Current draw | 2 / 2,4 / 1,15 / 1,4 A |
| Starting current | 10,6 / 12,1 / 6,1 / 7 A |
| Max. back pressure | 140 / 160 / 140 / 160 Pa |