ebm-papst Mulfingen GmbH & Co. KG W6D630-CN09-81
AC axial fan - HyBlade
Категории:
Технические характеристики
| Масса | 29,8 kg |
|---|---|
| Motor size | 110 |
| Size | 630 mm |
| Rotor surface | Painted black |
| Материал | Die-cast aluminum, painted black |
| Материал | Press-fitted, painted sheet steel blank, sprayed with PP plastic |
| Материал | Sheet steel, galvanized and coated with white aluminum plastic (RAL 9006) |
| Материал | Steel, coated with white-aluminum plastic (RAL 9006) |
| Number of blades | 5 |
| Airflow direction | A |
| Direction of rotation | Clockwise, viewed toward rotor |
| Degree of protection | IP54 |
| Insulation class | "F" |
| Рабочая температура | Occasional start-up at temperatures between -40°C and -25°C is permitted. For continuous operation at ambient temperatures below -25°C (such as refrigeration applications), use must be made of a fan design with special low-temperature bearings. |
| Moisture (F) / Environmental (H) protection class | H2+T |
| Max. permitted ambient temp. for motor (transport/storage) | + 80 °C |
| Min. permitted ambient temp. for motor (transport/storage) | - 40 °C |
| Installation position | Shaft horizontal or rotor on top; rotor on bottom on request |
| Condensation drainage holes | On stator side |
| Mode | S1 |
| Motor bearing | Ball bearing |
| Touch current according to IEC 60990 (measuring circuit Fig. 4, TN system) | <= 3,5 mA |
| Electrical hookup | Terminal box |
| Motor protection | Thermal switch auto reset, lead out, with basic insulation |
| Protection class assignment | I; If a protective earth is connected.|The built-in component has several local protection class assignments.|The final protection class is determined by the intended installation. |
| Conformity with standards | EN 60034-1 (2010) / CE |
| Approval | VDE / UL 1004-1 / CSA C22.2 No. 100 |
| Phase | 3~ / 3~ / 3~ / 3~ |
| Напряжение питания | AC / AC / AC / AC |
| Напряжение питания | 230 / 277 / 400 / 480 V |
| Connection | D / D / Y / Y |
| Frequency | 50 / 60 / 50 / 60 Hz |
| Type of data definition | running at free air / running at free air / running at free air / running at free air |
| Valid for approval / standard | CE / CE / CE / CE |
| Speed | 930 / 1090 / 930 / 1090 min-1 |
| Power input | 480 / 790 / 480 / 790 W |
| Current draw | 2,17 / 2,51 / 1,25 / 1,45 A |
| Starting current | 7,2 / 4,3 A |
| Max. back pressure | 110 / 80 / 110 / 80 Pa |
| Рабочая температура | -40 / -40 / -40 / -40 °C |