Honeywell International Inc. 02104-N-4051
Searchline Excel Open Path Infrared Gas Detector 02104-N-4051
Категории:
Технические характеристики
| Brand | Honeywell; Honeywell |
|---|---|
| Sub-Category | Infrared Gas Detectors & Transmitters |
| Alarm Settings | High 3 LEL.m; Low 1 LEL.m |
| Features & Benefits | 100% Solar Immune; Coaxial Optics Delivers Best-in Class Performance and Resilience to Partial Obscuration; Compatible with Existing Systems; Correct Operation Under Partial Obscuration Conditions; Double Band Pass Filters that Fully Compensate for All Types of Fog, Rain and/Mist Interference; Easier to Align with Greater Zoom and Magnification; FM Hazardous Area and Performance Approved; Fully Temperature Compensated Solid State Detectors; Guaranteed performance; High Vibration Resilience; High-Power Telescope; Higher Power and More Robust Design Telescope; Low Power Consumption in All Conditions; No Extra Software Alignment Required; Optional Modbus RS485 Multi Drop Output; Radially Symmetrical and Bonded Window Heating Delivers Good Low Temperature Performance; Reduced Sensitivity to Alignment; Reduced Sensitivity to Partial Obscuration; Robust Shock Resistant Design; Simple Confirmation of Alignment; Simple to Use, Accurate Alignment Tools; Simple ‘Lock On’ Alignment Tool; Visual Indication of Target and Current Signal Levels |
| Vibration | 2 to 60 Hz |
| Масса | Medium and Long Range TX: 7 kg and RX: 3.5 kg; Short Range TX: 3.5kg |
| Path Length | Long Range: 120m to 200m (390ft to 650ft); Medium Range: 40m to 120m (130 ft to 390 ft); Short Range: 5m to 40m (15ft to 130ft) |
| Humidity Range | 0 to 99% RH (Non-Condensing) |
| Calibration Gas | Methane, Ethane, Propane, Butane, Pentane, Ethylene, Propylene, Butadiene |
| Maximum Pressure | 105.5 Kpa |
| Warm Up Time | Less than 1 Hour (Fully Stabilized); Less than 5 min (Operational) |
| Speed of Response | T90 < 3 sec |
| Signal Output | 2 mA (1) 0 mA Fault; 2.5 mA (1) Beam Blocked; 21 mA Over Range; 3 mA (1) Dirty Optics; 4 to 20 mA (Max Loop Resistance 600 ohms; Source and Sink Available) and RS485; 4 to 20 mA Normal Operation (0 to 5 LEL.m) |
| Misalignment Tolerance | Long Range: ± 0.5º (±~170 cm @200m); Medium Range: ± 0.5° (±~104 cm @120m); Short Range: ± 0.5° (±~35 cm @40m) |
| Measuring Range | 0 to 5 LEL.m |
| Digital Output | Modbus RS485 Multi Drop. (Using DX100(M)); XNX Universal Transmitter with Modbus Option |
| Minimum Temperature | -40˚C |
| Ingress Protection | IP66; IP67 |
| Power Requirement | 18 to 32 VDC |
| Power Consumption | Medium and Long Range Tx: 10W/13W and Rx: 8W; Short Range Tx: 3.5W/5.0W |
| Материал | 316 Stainless Steel |
| Application | Downstream Chemical Processing Plants; Gas Transport and Pipelines; Large Storage Areas and Buildings; Off-Shore Platforms & Vessels (FPSO’s); Perimeter Detection |
| Industry | Energy; Logistics & Warehouses |
| description | XL ATEX MR SI DVC KIT |