1290K0064

Honeywell International Inc. 1290K0064

Vertex™ M Toxic Gas Monitoring System 1290K0064

Категории:

Технические характеристики

BrandHoneywell
Alarm TypeCapable of A1 and A2 Alarms per Point, per Point Maintenance/Instrument Faults, as well as General Analyzer A1, General Analyzer A2, and General Analyzer Instrument/Maintenance Faults
Visual Indicators1024 x 768 pixel Touch Screen with at-a-Glance System Status
Features & Benefits8 to 24 Point Toxic Gas Monitor Configurable for Use with up to 3 Universal Chemcassette Analyzers or Combination 1 Pyrolyzer Analyzer/1 Universal Chemcassette Analyzer
Display Type1024 x 768 pixel Touch Screen with at-a-Glance System Status
SizeH: 56 in D: 36 in W: 24 in
Sampling DistanceUp to 400ft
Exhaust Length50 ft
Sample LinesID: 0.156 in OD: 1/4 in FEP Teflon; ID: 0.190 in OD: 1/4 in FEP Teflon
RelaysIsolated (08X) or Non-Isolated (016X); PLC: 32 Relays for 8 Channel Isolated Relay Option; 64 Relays Total for 16 Channel Non-Isolated Relay Option
Operating Altitude-1,000 ft to 6,000 ft Above Sea Level
Network InterfaceOLE for Process Control (OPC) Interface
Exhaust LineID: 3/8 in OD: 1/2 in Polypropylene
Digital Communication PortsControlNet; DF1; DeviceNet; Ethernet/CIP; LonWorks; ModBus Plus; Modbus/TCP; Profibus - DP
Analog Outputs4 to 20 mA (24 Channels)
Power Requirement110/230 V AC
Напряжение питания110 or 230 V AC ± 10% (Under Load) @50/60 Hz; 15A
Operating Humidity20 to 65% RH
For Use WithUniversal Chemcassette Analyzers and Pyrolyzer Analyzer
СертификацияCE Certified; EN 300 330-1 V1.8.1; EN 301 489-1 V1.9.2; EN 50270:2015; EN 61010-1:2010; EN IEC 63000:2018; EN ISO/IEC 17050-1:2010; RoHS
IndustryManufacturing
descriptionFloor Mounting Option