ifm electronic gmbh AC514A
AS-Interface ClassicLine module with quick mounting technology, ClassicL 2DO-Y 2DI-Y II 3D
Категории:
Технические характеристики
| Design | housing for DIN rail mounting |
|---|---|
| Application | AS-i ATEX module |
| Напряжение питания | 26.5...31.6 DC |
| Max. current consumption from AS-i [mA] | 150 |
| Max. current load total [A] | 2 |
| Integrated watchdog | yes |
| Number of inputs and outputs | Number of digital inputs: 2; Number of digital outputs: 2 |
| Number of digital inputs | 2 |
| Input circuit of digital inputs | PNP |
| Sensor supply of the inputs | AS-i |
| Напряжение питания | 18...30; (via flat cable) |
| Max. total current rating of inputs [mA] | 100 |
| Input current High [mA] | 6...10 |
| Input current low [mA] | 0...2 |
| Switching level high [V] | > 11 |
| Digital inputs protected against short circuits | yes |
| Number of digital outputs | 2 |
| Circuit | PNP |
| Напряжение питания | 15...30; (to PELV; via flat cable) |
| Max. current load per output [mA] | 1000; (utilization category DC-13 (control of electromagnets): 20 W (IEC 60947-5-1)) |
| Short-circuit proof | yes |
| Electrically separated | yes |
| Рабочая температура | -10...50 |
| Protection | IP 50 |
| ATEX marking | II 3D Ex tc IIIB T80°C Dc X IP50 |
| EMC | EN 50295; IEC 61000-6-2 |
| MTTF [years] | 192 |
| AS-i version | 2.11; 3.0 |
| AS-i addressing | Addressing socket |
| Extended addressing mode | yes |
| AS-i master profile | M2; M3; M4 |
| AS-i profile | S-B.A.E |
| AS-i I/O configuration [hex] | B |
| AS-i ID code [hex] | A.E |
| Сертификация | yes |
| Data bits | Data bit: D0: D1: D2: D3; Input: -: -: 3: 4; Socket: -: -: I-3/4: I-3/4 I-4; Pin: -: -: 4: 2 4; Output: 1: 2: -: -; Socket: O-1/2: O-1/2 / O-2: -: -; Pin: 4: 2 4: -: - |
| Масса | 239.5 |
| Housing | rectangular |
| Type of mounting | AS-i flat cable connection; Mounting on DIN rail; (TH35 (EN 60715)) |
| Dimensions [mm] | 103 x 45 x 44.7 |
| Материал | PA; Piercing contacts: CuSn6 nickel-plated and tin-plated |
| Display | Power: LED, green; errors: LED, red; Function: LED, yellow |
| Module connection | Flat cable |
| Items supplied | lower part |
| Accessories (optional) | Protective cap: M12, E73004; impact protection housing:, E7000A |
| Remarks | Mechanical protection has to be implemented.; Otherwise the unit must be installed together with the impact protection housing (E7000A).; Do not connect any of the following points to an external potential:; I-, I+, I-3/4, I-4; The connections are electrically connected with the AS-i cable.; Inputs and outputs must be electrically isolated. |
| Pack quantity | 1 pcs. |
| quick mounting technology for AS-i flat cable | ; three selectable directions |
| Connector | M12 |