ifm electronic gmbh AL2627
IO-Link input/output module, IOL MOD PL 8XDX/DX E D M12 IP67
Технические характеристики
| Напряжение питания | 18...30 DC |
|---|---|
| Current consumption [mA] | 100; (US) |
| Protection class | III |
| Напряжение питания | 18...30 DC; (UA) |
| Max. current consumption from additional supply [mA] | 16000; (UA) |
| Total number of inputs and outputs | 16 |
| Number of inputs and outputs | Number of digital inputs: 16; Number of digital outputs: 16 |
| Number of digital inputs | 16; (configurable) |
| Input circuit of digital inputs | PNP; (type 3 (IEC 61131-2)) |
| Sensor supply of the inputs | AUX (UA) |
| Напряжение питания | 18...30 |
| Input current High [mA] | 2...15 |
| Input current low [mA] | 0...1.5 |
| Switching level high [V] | 11...28 |
| Switching level low [V] | 0...5 |
| Number of digital outputs | 16; (configurable) |
| Max. current load per output [mA] | 2000 |
| Max. current load outputs total [A] | 16 |
| Short-circuit protection | yes |
| Actuator supply outputs | AUX (UA) |
| Communication interface | IO-Link |
| Transmission type | COM3 (230,4 kBaud) |
| IO-Link revision | 1.1 |
| SDCI standard | IEC 61131-9 |
| Profiles | Common - I&D: Identification and Diagnosis |
| SIO mode | no |
| Required master port class | A |
| Min. process cycle time [ms] | 4 |
| Supported DeviceIDs | Type of operation: DeviceID; default: 1314 |
| Note | Parameterization can be changed from cyclical to acyclical.; For further information please see the IODD PDF file at "Downloads" |
| Рабочая температура | -25...60 |
| Storage temperature [°C] | -25...70 |
| Max. relative air humidity [%] | 90 |
| Max. height above sea level [m] | 2000 |
| Protection | IP 65; IP 67 |
| Protection rating (NEMA 250) | 6P |
| Pollution degree | 2 |
| Chemical media | ISO 16750-5: AA, BA, BD, HLP, CC, DB, DC, DD, CA; NEMA 250 5.13.1: AA |
| EMC | EN 61000-6-2; EN 61000-6-4; IEC 61131-9 |
| Shock resistance | DIN EN 60068-2-27 |
| Vibration resistance | DIN EN 60068-2-64; DIN EN 60068-2-6 |
| MTTF [years] | 59 |
| Complies with the requirements | ISO 13849-1 PL d |
| Масса | 399 |
| Dimensions [mm] | 26 x 59.3 x 208 |
| Материал | housing: PA orange; Socket: brass nickel-plated |
| Материал | FKM |
| Tightening torque [Nm] | < 0.8 |
| Display | Power: 1 x LED, green; fault: 1 x LED, red; Function: 1 x LED, yellow |
| Accessories (optional) | protective cap for M12 sockets |
| Remarks | Using the device within a system with requirements for functional safety is possible by deactivating the actuator voltage UA without interaction.; For further information on functional safety, please refer to the operating instructions supplement under “Downloads”. |
| Pack quantity | 1 pcs. |
| Connector | 8 x M12; coding: A; Contacts: 4; sealing: FKM |