ifm electronic gmbh DL3003
Evaluation unit for monitoring analog standard signals, MONITOR/ANALOG/IOL/AC/DC
Технические характеристики
| Communication interface | IO-Link |
|---|---|
| Housing | rectangular |
| Dimensions [mm] | 126 x 50 x 112.4 |
| Design | housing for DIN rail mounting |
| Application | 2-channel analog threshold relay for analog standard signals |
| Напряжение питания | 110...240 AC / 18...30 DC; (tolerance AC operation: -20 % / +10 %) |
| Напряжение питания | 110...240 |
| Напряжение питания | 24 |
| Nominal frequency AC [Hz] | 50...60 |
| Current consumption [mA] | AC operation: max. 8 A (including maximum AC supply for additional devices ) |
| Max. power consumption DC [W] | 9 |
| Напряжение питания | II |
| Auxiliary energy for sensors DC [V] | 16.5...27.7; (Short-circuit proof; DC operation: ≤ 200 mA; AC operation: ≤ 150 mA) |
| Number of inputs and outputs | Number of analog inputs: 2; Number of digital outputs: 2; Number of analog outputs: 1; Number of relay outputs: 2 |
| Number of analog inputs | 2; (configurable) |
| Analog input (current) [mA] | 0...20 |
| Input resistance [Ω] | 300 |
| Напряжение питания | 0...10 |
| Input resistance [kΩ] | 25 |
| Resolution of analog input | 12 Bit |
| Number of digital outputs | 2 |
| Number of relay outputs | 2; (changeover contact) |
| Number of analog outputs | 1 |
| Circuit | PNP |
| Max. current load per output [mA] | 10 |
| Short-circuit proof | yes |
| Electrically separated | no |
| Minimum load current [mA] | 10; (> 12 V) |
| Contact rating | 6 A; (max. 240 V AC / 30 V DC see diagram:: Contact rating; B300: 6000 cycles) |
| Switching frequency AC [Hz] | < 2 |
| Switching frequency DC [Hz] | < 2 |
| Analog current output [mA] | 4...20; (max.. 20,5 mA) |
| Max. load [Ω] | 600; (300 Ω: Operating voltage < 24 V DC) |
| Accuracy | ± 0.75; (% of the final value < 45 °C; including analog input accuracy) |
| Temperature coefficient [% of the span / 10 K] | ± 0,1; (> 45 °C) |
| Transmission type | COM2 (38,4 kBaud) |
| IO-Link revision | 1.1 |
| SDCI standard | IEC 61131-9 |
| Profiles | Smart Sensor - SSP 4.1.2: Measuring and Switching Sensor, 2 channel; Common - I&D: Identification and Diagnosis; Extension: Sensor control; Extension: Quantity detection, switches when value exceeds the setpoint; Function: Locator; Function: ProductURI |
| Required master port class | A |
| Min. process cycle time [ms] | 4.9 |
| Supported DeviceIDs | Type of operation: DeviceID; default: 1583 |
| Рабочая температура | -40...60 |
| Рабочая температура | 110V AC operation: -25...60 °C; 2000...3000 m: max. 58 °C; 3000...4000 m: max. 56 °C; Contact rating Relay output: B300 max. 50 °C |
| Storage temperature [°C] | -40...85 |
| Max. relative air humidity [%] | 80; (31 °C; linearly decreasing to 50 % (40 °C)) |
| Max. height above sea level [m] | 4000 |
| Protection | IP 20; (when mounted) |
| Protection rating terminals | IP 20 |
| Pollution degree | 2 |
| EMC | EN 61000-6-2; EN 61000-6-8 |
| Electrical safety | EN 61010-1; EN 61010-2-201 |
| MTTF [years] | 150 |
| UL approval | Ta: 60 °C; Enclosure type: open Type; File number UL: E191692 |
| Масса | 338.6 |
| Type of mounting | Mounting on DIN rail; (TH35 (EN 60715)) |
| Материал | housing: plastics |
| Display | 1x OLED display, 128 x 64 pixels luminous; Switching status: 2x LED, yellow; Power: 1x LED, green/red |
| Teach function | yes |
| Items supplied | cage clamps: 9 |
| Remarks | For information about installation and operation please see the operating instructions. |
| Pack quantity | 1 pcs. |
| cage clamps | ...2.5 mm² |