DU110S

ifm electronic gmbh DU110S

Evaluation unit for safe speed monitoring, Safety underspeed Monitor

  • Бренд: ifm electronic gmbh
  • Артикул (MPN): DU110S
  • Статус производства: Не определён

Категории:

Технические характеристики

Housingrectangular
Dimensions [mm]108 x 22.5 x 114.5
Electrical designPNP
Output function1 x error output "Fault"; 1 x Diagnostic output "Underspeed"
Designhousing for DIN rail mounting
Applicationreliable evaluation of rotating and linear movements with regard to underspeed
Напряжение питания19.2...28.8 DC; (incl. 5 % residual ripple)
Напряжение питания24
Current consumption [mA]< 125
Protection classII
Max. power-on delay time [ms]3000
Auxiliary energy for sensors DC [V]24; (≤ 70 mA , voltage drop relative to the operating voltage ≤ 2 V)
Number of inputs and outputsNumber of digital outputs: 2; Number of relay outputs: 2
Input characteristicsS34, S43: "1": 6 mA / 24 V DC
Input circuit of digital inputsPNP
Current through feedback contacts [mA]< 100
Number of digital outputs2
Number of relay outputs2
Short-circuit proofyes
Contact rating6 A, 250 V AC / 24 V DC; (≥ 6 mA ; resistive load)
Type of short-circuit protectionThe contacts are to be protected by means of external fuses with a nominal current of < 3.6 A
Max. current load per output [mA]20; (24 V DC, voltage drop relative to the supply voltage ≤ 2 V, non-safe)
Setting range Hz [Hz]0.5...990
Setting range [Imp/min]10...49500
Frequency range [Hz]< 2000; (pulse duration: 100 µs: > 500 Hz ; 150 µs: ≤ 500 Hz)
Hysteresis [%]5
Notes on the accuracy / deviationPermitted frequency difference between the inputs: ≤ 10 % (f > 100 Hz) / ≤ 20 % (f < 100 Hz)
Время откликаf sel ≥ 100 Hz:: t = 10,7 + 400 x (f sel ÷ f in); f sel < 100 Hz:: t = 14 + (4500 ÷ f in)
Время отклика5.5
Legendt :: Response time; f sel :: set frequency (preset value); f in :: applied frequency (actual value)
Рабочая температура-40...55
Рабочая температураobserve the free space for convection (see operating instructions)
Storage temperature [°C]-40...70
Max. relative air humidity [%]95
Max. height above sea level [m]2000
ProtectionIP 20
Complies with the requirementsISO 13849-1 Category 4, PL e; IEC 61508 SIL 3
MIssion time TM [h]≤175200
Mission time TM (additional indication)20 years
PFH [1/h]DC13 (2 A), 24 V DC: 7,69E-09; AC15 (1 A), 230 V AC: 8,25E-09; AC15 (3 A), 230 V AC: 9,15E-09
Hardware Failure Tolerance HFT1; (Type B)
Масса343
Type of mountingMounting on DIN rail; (TH35 (EN 60715))
Материалhousing: PA
DisplayVoltage: 1x LED, green; release: 1x LED, yellow; Configuration: 1x LED, blue; error: 1x LED, red; Switching status: 2x LED, green; input signal: 2x LED, yellow
Remarkssafety classification considering 1000 relay operations/year
Pack quantity1 pcs.
screw terminals0.5...2.5 mm²; AWG 30...12
Получить предложение по этой позиции