DW3003

ifm electronic gmbh DW3003

evaluation unit for monitoring and converting frequency signals, MONITOR/FREQUENCY/IOL/AC/DC

  • Бренд: ifm electronic gmbh
  • Артикул (MPN): DW3003
  • Статус производства: Не определён

Технические характеристики

Communication interfaceIO-Link
Housingrectangular
Dimensions [mm]126 x 50 x 112.4
Designhousing for DIN rail mounting
ApplicationConversion of pulse sequences into analog standard signals; pulse evaluation system for frequency, rotational speed, speed, cycles and machine cycles
Напряжение питания110...240 AC / 18...30 DC; (tolerance AC operation: -20 % / +10 %)
Напряжение питания110...240
Напряжение питания24
Nominal frequency AC [Hz]50...60
Current consumption [mA]AC operation: max. 8 A (including maximum AC supply for additional devices )
Max. power consumption DC [W]9
Напряжение питанияII
Auxiliary energy for sensors DC [V]16.5...27.7; (Short-circuit proof; DC operation: ≤ 200 mA; AC operation: ≤ 150 mA)
Number of inputs and outputsNumber of digital inputs: 3; Number of digital outputs: 2; Number of analog outputs: 1; Number of relay outputs: 2
Number of digital inputs3; (1 x Frequency 1 x Reset 1 x Restart)
Input circuit of digital inputsPNP; (type 3 (IEC 61131-2))
Input current High [mA]2...4
Input current low [mA]0...1.5
Switching level high [V]11...28
Switching level low [V]0...5
Number of digital outputs2
Number of relay outputs2; (changeover contact)
Number of analog outputs1; (configurable)
CircuitPNP
Max. current load per output [mA]10
Short-circuit proofyes
Electrically separatedno
Minimum load current [mA]10; (> 12 V)
Contact rating6 A; (max. 240 V AC / 30 V DC see diagram:: Contact rating; B300: 6000 cycles)
Switching frequency AC [Hz]< 2
Switching frequency DC [Hz]< 2
Analog current output [mA]4...20; (max. 20,5 mA)
Max. load [Ω]600; (300 Ω: Operating voltage < 24 V DC)
Напряжение питания0...10
Min. load resistance [Ω]2000
Setting range Hz [Hz]0.1...10000
Measuring range [U/min]6...900000
Measuring range [Hz]0.1...15000
Accuracy± 0.6; (% of the final value)
Transmission typeCOM2 (38,4 kBaud)
IO-Link revision1.1
SDCI standardIEC 61131-9
ProfilesSmart Sensor - SSP 4.2.1: Measuring and Switching Sensor, high resolution, 1 channel; Common - I&D: Identification and Diagnosis; Extension: Sensor control; Extension: Quantity detection, switches when value exceeds the setpoint; Function: Locator; Function: ProductURI
Required master port classA
Min. process cycle time [ms]4.3
Supported DeviceIDsType of operation: DeviceID; default: 1584
Рабочая температура-40...60
Рабочая температура110V AC operation: -25...60 °C; 2000...3000 m: max. 58 °C; 3000...4000 m: max. 56 °C; Contact rating Relay output: B300 max. 50 °C
Storage temperature [°C]-40...85
Max. relative air humidity [%]80; (31 °C; linearly decreasing to 50 % (40 °C))
Max. height above sea level [m]4000
ProtectionIP 20; (when mounted)
Protection rating terminalsIP 20
Pollution degree2
EMCEN 61000-6-2; EN 61000-6-8
Electrical safetyEN 61010-1; EN 61010-2-201
Масса336.1
Type of mountingMounting on DIN rail; (TH35 (EN 60715))
Материалhousing: plastics
Display1 x OLED display, 128 x 64 pixels luminous; Switching status: 2 x LED, yellow; Power: 1 x LED, red/green
Items suppliedcage clamps: 8
RemarksFor information about installation and operation please see the operating instructions.
Pack quantity1 pcs.
cage clamps...2.5 mm²
Получить предложение по этой позиции