ifm electronic gmbh E43406
IO-Link data splitter, IO-LINK DATA SPLITTER PNP
Технические характеристики
| Number of inputs and outputs | Number of digital outputs: 1 |
|---|---|
| Special feature | gold-plated contacts |
| Application | for retrofitting of existing IO-Link systems; for systems without IO-Link capabilities |
| Напряжение питания | 18...30 DC; (on the master side; on the controller / system: 20...30 DC) |
| Напряжение питания | 24 |
| Current consumption [mA] | < 17; (both sides) |
| Protection class | III |
| Reverse polarity protection | yes; (on the master side) |
| Power-on delay time [s] | < 2; (for communication; response time switching signal: response time device added with IO-Link process cycle time) |
| Total number of inputs and outputs | 1; (on the controller / system) |
| Output signal | switching signal; IO-Link |
| Electrical design | PNP |
| Number of digital outputs | 1 |
| Output function | normally open / closed |
| Напряжение питания | 2.5 |
| Permanent current rating of switching output DC [mA] | 200 |
| Type of short-circuit protection | yes (non-latching) |
| Short-circuit proof | yes |
| Overload protection | yes |
| Communication interface | IO-Link |
| Supported DeviceIDs | Type of operation: DeviceID; IO-Link Device: 1107 |
| Note on interfaces | connection to IO-Link enabled auxiliary devices |
| Transmission type | COM1 (4,8 kBaud); COM2 (38,4 kBaud); COM3 (230,4 kBaud) |
| IO-Link revision | 1.0; 1.1 |
| SDCI standard | IEC 61131-9 |
| Profiles | Smart Sensor - SSP 0: Generic Profiled Sensor; Function: Device identification; Function: Process data variable; Function: Device diagnosis; Function: Extended identification |
| SIO mode | yes |
| Required master port class | A |
| Min. process cycle time [ms] | 4.2 |
| Unterstützte Masterportklasse | A / B |
| Рабочая температура | -25...60 |
| Storage temperature [°C] | -25...70 |
| Protection | IP 67 |
| EMC | DIN EN 61000-6-2; DIN EN 61000-6-4: in plastic or open metal tanks |
| Shock resistance | DIN EN 60068-2-27: 15 g (6 ms) |
| Vibration resistance | DIN EN 60068-2-6: 2 g (10...150 Hz) |
| MTTF [years] | 307 |
| UL approval | Ta: max. 55 °C; File number UL: E205959 |
| Масса | 90 |
| Материал | stainless steel (1.4404 / 316L); brass (2.0401); PBT; PA; sealing: FKM; |
| Display | Switching output: 1 x LED, yellow; Power: 1 x LED, green; IO-Link: 1 x LED, yellow |
| Accessory required | Y connection cable 1, EVC843 |
| Remarks | For information on the maximum cable length please refer to the operating instructions.; To ensure the function according to technical datasheet and operating instructions the use of the following article is imperative: EVC843; the device complies with overvoltage category II |
| Pack quantity | 1 pcs. |