Технические характеристики
| Output function | normally open |
|---|---|
| Sensing range [mm] | 8 |
| Housing | Threaded type |
| Dimensions [mm] | M18 x 1 / L = 80 |
| Application | For applications in hazardous areas |
| Installation | use in hazardous areas only with installed protective cover |
| Напряжение питания | 20...250 AC/DC |
| Protection class | II |
| Reverse polarity protection | yes |
| Напряжение питания | 6 |
| Напряжение питания | 6.5 |
| Minimum load current [mA] | 5 |
| Max. leakage current [mA] | 2.5 (250 V AC) / 1.3 (130 V AC) / 0.8 (24 V DC) |
| Permanent current rating of switching output AC [mA] | 150 |
| Permanent current rating of switching output DC [mA] | 100 |
| Short-time current rating of switching output [mA] | 2200; (20 ms / 0,5 Hz) |
| Switching frequency AC [Hz] | 25 |
| Switching frequency DC [Hz] | 50 |
| Notes on switching frequency [Hz] | only for resistive loads; 2 Hz for utilization category AC-140 |
| Short-circuit protection | no |
| Overload protection | no |
| Real sensing range Sr [mm] | 8 ± 10 % |
| Operating distance [mm] | 0...6.48 |
| Correction factor | steel: 1 / stainless steel: 0.7 / brass: 0.4 / aluminum: 0.3 / copper: 0.2 |
| Hysteresis [% of Sr] | 1...20 |
| Switch-point drift [% of Sr] | -10...10 |
| Рабочая температура | -20...60 |
| Protection | IP 67 |
| ATEX marking | II 3D Ex tc IIIC T80°C Dc X |
| EMC | EN 61000-4-2 ESD: 4 kV CD / 8 kV AD; EN 61000-4-3 HF radiated: 3 V/m; EN 61000-4-4 Burst: 2 kV; EN 61000-4-6 HF conducted: 3 V; IEC 60255-5: 1 kV line to line, Ri: 500 Ohm; EN 55011 emission: class B |
| MTTF [years] | 604 |
| Масса | 184.5 |
| Mounting | non-flush mountable |
| Thread designation | M18 x 1 |
| Материал | housing: brass white bronze coated; lock nuts: brass white bronze coated; sensing face: PBT; Protective cover: PA |
| Display | Switching status: 1 x LED, yellow |
| Required protection | miniature fuse to IEC60127-2 sheet 1; ≤ 2 A; fast acting; Place the fuse outside the hazardous area. |
| Items supplied | lock nuts: 3 x M18; Protective cover: 1 x (M18 / Ø 23 mm) |
| Remarks | Recommendation: check the unit for reliable function after a short circuit. |
| Pack quantity | 1 pcs. |
| Cable | 2 m, PVC; 2 x 0.50 mm² |