ifm electronic gmbh II5914
inductive analog sensor with IO-Link, IIK4015A2PKG/IO/US
Категории:
Технические характеристики
| Electrical design | PNP/NPN; (configurable) |
|---|---|
| Output function | normally open / closed; (configurable) |
| Communication interface | IO-Link |
| Housing | Threaded type |
| Dimensions [mm] | M30 x 1.5 / L = 65 |
| Напряжение питания | 15...30 DC |
| Current consumption [mA] | < 30 |
| Protection class | II |
| Reverse polarity protection | yes |
| Напряжение питания | 2.5 |
| Permanent current rating of switching output DC [mA] | 100 |
| Switching frequency DC [Hz] | 300 |
| Напряжение питания | 0...10; (linear; gradient: 0,714 V/mm; for frontal approach and for target made of mild steel: 45 x 45 x 1 mm) |
| Min. load resistance [Ω] | 2000 |
| Short-circuit protection | yes |
| Overload protection | yes |
| Measuring range [mm] | 1...15 |
| Switch point IO-Link [mm] | 2.37...13.99 |
| Correction factor | steel: 1 / stainless steel: 0.7 / brass: 0.4 / aluminum: 0.4 / copper: 0.3 |
| Hysteresis [% of Sr] | 3...15 |
| Note on hysteresis | configurable |
| Linearity error of analog output [%] | ± 1; (of the final value of the measuring range) |
| Repeatability analog output [%] | ± 1; (of the final value of the measuring range) |
| Temperature coefficient [%/K vom MEW] | ±0,15 |
| Temperature drift | ± 5 %; (of the final value of the measuring range) |
| Время отклика | < 10 |
| Transmission type | COM2 (38,4 kBaud) |
| IO-Link revision | 1.1 |
| SDCI standard | IEC 61131-9 |
| Profiles | Smart Sensor - SSP 0: Generic Profiled Sensor; Common - I&D: Identification and Diagnosis; Function: Multiple switching signal; Function: Teach channel |
| SIO mode | yes |
| Required master port class | A |
| Min. process cycle time [ms] | 3.2 |
| IO-Link process data (cyclical) | Function: bit length; process value: 16; device status: 4; binary switching information: 2 |
| IO-Link functions (acyclical) | switching cycles counter; switch-on cycle counter; operating hours counter; internal temperature; application specific tag |
| Supported DeviceIDs | Type of operation: DeviceID; default: 1206 |
| Note | For further information please see the IODD PDF file at "Downloads" |
| Рабочая температура | -25...80 |
| Protection | IP 65; IP 66; IP 67; IP 68; IP 69K |
| EMC | EN 61000-4-2 ESD: 4 kV CD / 8 kV AD; EN 61000-4-3 HF radiated: 10 V/m; EN 61000-4-4 Burst: 2 kV; EN 61000-4-6 HF conducted: 10 V; EN 55011: class B |
| Vibration resistance | EN 60068-2-6 Fc: 20 g (10...3000 Hz) / 50 sweep cycles per frequency; 1 octave per minute in 3 axes |
| Shock resistance | EN 60068-2-27 Ea: 100 g 11 ms half-sine; 3 shocks each in every direction of the 3 coordinate axes |
| Continuous shock resistance | EN 60068-2-27: 40 g 6 ms; 4000 shocks each in every direction of the 3 coordinate axes |
| Fast temperature changes | EN 60068-2-14 Na: TA = -25°C; TB = 80°C; t1 = 30 min; t2 = < 10 s 50 cycles |
| MTTF [years] | 222 |
| Embedded software included | yes |
| UL approval | Ta: -25...60 °C; Enclosure type: Type 1; voltage supply: Limited Voltage/Current; UL approval number: A024; File number UL: E174191 |
| Масса | 142 |
| Mounting | non-flush mountable |
| Thread designation | M30 x 1.5 |
| Материал | housing: brass white bronze coated; sensing face: PBT orange; LED window: PEI; lock nuts: brass white bronze coated |
| Tightening torque [Nm] | 50 |
| Display | target in measuring range: 4 x LED, yellow lights; target outside measuring range: 4 x LED, yellow flashing |
| Items supplied | lock nuts: 2 |
| Pack quantity | 1 pcs. |
| Connector | 1 x M12; coding: A; Contacts: 4 |