ifm electronic gmbh LR2350
Continuous level sensor (guided wave radar), LR0000BSEN34AKSKG/US
Категории:
Технические характеристики
| Number of inputs and outputs | Number of digital outputs: 1; Number of analog outputs: 1 |
|---|---|
| Probe length L [mm] | 150...2000 |
| Process connection | threaded connection 3/4" NPT external thread |
| Special feature | gold-plated contacts |
| Application | for industrial applications |
| Media | Liquids |
| Dielectric constant of the medium | > 5 |
| Recommended media | water; water-based media |
| Process temperature [°C] | -20...100; (see note under remarks) |
| Pressure rating | 16 bar: 1.6 MPa |
| Vacuum resistance | -1000 mbar: -0.1 MPa |
| MAWP (for applications according to CRN) [bar] | 16 |
| Напряжение питания | 18...30 DC |
| Current consumption [mA] | < 50 |
| Protection class | III |
| Reverse polarity protection | yes |
| Power-on delay time [s] | < 3 |
| Measuring principle | guided wave radar |
| Total number of outputs | 2 |
| Output signal | switching signal; analog signal; IO-Link |
| Electrical design | PNP/NPN |
| Number of digital outputs | 1 |
| Output function | normally open / closed; (configurable) |
| Напряжение питания | 2.5 |
| Permanent current rating of switching output DC [mA] | 150; (200 (...60 °C)) |
| Number of analog outputs | 1 |
| Analog current output [mA] | 4...20, invertible; (scalable) |
| Max. load [Ω] | 500 |
| Short-circuit protection | yes |
| Type of short-circuit protection | yes (non-latching) |
| Overload protection | yes |
| Active range A [mm] | L-40 |
| Inactive range I1 / I2 [mm] | 30 / 10 |
| Sampling rate [Hz] | 4 |
| Set point SP [mm] | 15...L-30 |
| Reset point rP [mm] | 10... L-35 |
| In steps of [mm] | 1 |
| Hysteresis [mm] | > 5 |
| Measuring error [mm] | ± 7 |
| Offset error [mm] | 5 |
| Resolution [mm] | 1 |
| Zero signal (current) [mA] | 4.0 |
| Full signal (current) [mA] | 20 |
| Temperature drift per 10 K | ± 0.2 % |
| Communication interface | IO-Link |
| Transmission type | COM2 (38,4 kBaud) |
| IO-Link revision | 1.1 |
| SDCI standard | IEC 61131-9 |
| Profiles | Smart Sensor - SSP 0: Generic Profiled Sensor; Function: Device identification; Function: Process data variable; Function: Device diagnosis |
| SIO mode | yes |
| Required master port class | A |
| Process data analog | 1 |
| Process data binary | 2 |
| Min. process cycle time [ms] | 2.3 |
| Supported DeviceIDs | Type of operation: DeviceID; default: 730 |
| Рабочая температура | -40...80 |
| Storage temperature [°C] | -40...100 |
| Protection | IP 68; IP 69K |
| EMC | DIN EN 61000-6-2; DIN EN 61000-6-3: : in a closed metal tank; DIN EN 61000-6-4: : in plastic or open metal tanks |
| Shock resistance | DIN EN 60068-2-27: 50 g (11 ms) / 20 g (6 ms) with reference rod 0.5 m |
| Vibration resistance | DIN EN 60068-2-6: 20 g (10...2000 Hz) / 1 g (5...200 Hz) with reference rod 0.5 m |
| MTTF [years] | 216 |
| Масса | 383.5 |
| Dimensions [mm] | Ø 50 / L = 128 |
| Материал | stainless steel (1.4404 / 316L); PEI; PFA; PBT; FKM |
| Материал | stainless steel (1.4404 / 316L); stainless steel (1.4435 / 316L); PTFE; FKM |
| Display | Display unit: 3 x LED, green; Switching status: 2 x LED, yellow; Level: alphanumeric display, 4-digit; Parameter setting: alphanumeric display, 4-digit |
| Notes | For high process temperatures: The temperature at the process connection is decisive. The actual medium temperature may be higher. |
| Pack quantity | 1 pcs. |
| Connector | 1 x M12; coding: A; Contacts: 4, gold-plated |