ifm electronic gmbh PN2015
Pressure sensor with display, PN-006-RER14-MFRKG/US/ /V
Категории:
Технические характеристики
| Number of inputs and outputs | Number of digital outputs: 2; Number of analog outputs: 1 |
|---|---|
| Measuring range | -1...6 bar: -14.5...87 psi: -100...600 kPa |
| Process connection | threaded connection G 1/4 Internal thread (DIN EN ISO 1179-2) |
| Special feature | gold-plated contacts |
| Measuring element | ceramic-capacitive pressure measuring cell |
| Application | for industrial applications |
| Media | liquids and gases |
| Medium temperature [°C] | -25...80 |
| Min. burst pressure | 100 bar: 1500 psi: 10000 kPa |
| Pressure rating | 40 bar: 600 psi: 4000 kPa |
| Vacuum resistance | -1000 mbar: -0.1 MPa |
| Type of pressure | relative pressure; vacuum |
| Напряжение питания | 18...30 DC; (to SELV/PELV) |
| Current consumption [mA] | < 35 |
| Min. insulation resistance [MΩ] | 100; (500 V DC) |
| Protection class | III |
| Reverse polarity protection | yes |
| Power-on delay time [s] | 0.3 |
| Integrated watchdog | yes |
| Total number of outputs | 2 |
| Output signal | switching signal; analog signal; IO-Link; (configurable) |
| Electrical design | PNP/NPN |
| Number of digital outputs | 2 |
| Output function | normally open / closed; (configurable) |
| Напряжение питания | 2 |
| Permanent current rating of switching output DC [mA] | 250 |
| Switching frequency DC [Hz] | < 500 |
| Number of analog outputs | 1 |
| Analog current output [mA] | 4...20; (scalable 1:5) |
| Max. load [Ω] | 500 |
| Напряжение питания | 0...10; (scalable 1:5) |
| Min. load resistance [Ω] | 2000 |
| Short-circuit protection | yes |
| Type of short-circuit protection | yes (non-latching) |
| Overload protection | yes |
| Set point SP | -0.95...6 bar: -13.8...87 psi: -95...600 kPa |
| Reset point rP | -0.98...5.97 bar: -14.2...86.6 psi: -98...597 kPa |
| Analog start point | -1...4.8 bar: -14.5...69.6 psi: -100...480 kPa |
| Analog end point | 0.2...6 bar: 2.9...87 psi: 20...600 kPa |
| Min. difference between SP and rP | 0.03 bar: 0.5 psi: 3 kPa |
| In steps of | 0.001 bar: 0.1 psi: 1 kPa |
| Switch point accuracy [% of the span] | < ± 0,4; (Turn down 1:1) |
| Repeatability [% of the span] | < ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1) |
| Characteristics deviation [% of the span] | < ± 0,25 (BFSL) / < ± 0,5 (LS); (Turn down 1:1; BFSL = Best Fit Straight Line; LS = limit value setting) |
| Hysteresis deviation [% of the span] | < ± 0,1; (Turn down 1:1) |
| Long-term stability [% of the span] | < ± 0,05; (Turn down 1:1; per 6 months) |
| Temperature coefficient zero point [% of the span / 10 K] | < ± 0,2; (-0...80 °C) |
| Temperature coefficient span [% of the span / 10 K] | < ± 0,2; (-0...80 °C) |
| Notes on the accuracy / deviation | switch point accuracy, linearity error under DNV GL: < ± 1%: < ± 1% |
| Время отклика | < 1.5 |
| Delay time programmable dS, dr [s] | 0...50 |
| Damping process value dAP [s] | 0...4 |
| Damping for the analog output dAA [s] | 0...4 |
| Время отклика | 3 |
| Parameter setting options | hysteresis / window; normally open / closed; switch-on/switch-off delay; Damping; Display unit; current/voltage output |
| Communication interface | IO-Link |
| Transmission type | COM2 (38,4 kBaud) |
| IO-Link revision | 1.1 |
| SDCI standard | IEC 61131-9 |
| Profiles | Smart Sensor - SSP 3.1: Measuring Sensor; Common - I&D: Identification and Diagnosis |
| SIO mode | yes |
| Required master port class | A; (when pin 2 not connected: B) |
| Min. process cycle time [ms] | 3 |
| IO-Link resolution pressure [bar] | 0.002 |
| IO-Link process data (cyclical) | Function: bit length; pressure: 16; device status: 4; binary switching information: 2 |
| IO-Link functions (acyclical) | application specific tag |
| Supported DeviceIDs | Type of operation: DeviceID; default: 1203 |
| Note | For further information please see the IODD PDF file at "Downloads" |
| Рабочая температура | -25...80 |
| Storage temperature [°C] | -40...100 |
| Protection | IP 65; IP 67 |
| EMC | DIN EN 61000-6-2; DIN EN 61000-6-3 |
| Shock resistance | DIN EN 60068-2-27: 50 g (11 ms) |
| Vibration resistance | DIN EN 60068-2-6: 20 g (10...2000 Hz) |
| MTTF [years] | 167 |
| UL approval | UL approval number: J012; File number UL: E174189 |
| Pressure equipment directive | sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
| Масса | 246.1 |
| Housing | tubular |
| Dimensions [mm] | Ø 34 / L = 90.7 |
| Материал | stainless steel (1.4404 / 316L); PBT+PC-GF30; PBT-GF20; PC |
| Материал | stainless steel (1.4404 / 316L); Al2O3 (ceramics); FKM |
| Min. pressure cycles | 100 million |
| Tightening torque [Nm] | 25...35; (recommended tightening torque; Depends on lubrication, seal and pressure rating) |
| Restrictor element integrated | no (can be retrofitted) |
| Display | Display unit: 3 x LED, green (bar, psi, MPa); Switching status: 2 x LED, yellow; Measured values: alphanumeric display, red/green 4-digit |
| Pack quantity | 1 pcs. |
| Connector | 1 x M12; coding: A; Contacts: 4, gold-plated |