PN2094

ifm electronic gmbh PN2094

Pressure sensor with display, PN-010-RER14-MFRKG/US/ /V

  • Бренд: ifm electronic gmbh
  • Артикул (MPN): PN2094
  • Статус производства: Не определён

Категории:

Технические характеристики

Number of inputs and outputsNumber of digital outputs: 2; Number of analog outputs: 1
Measuring range-1...10 bar: -14.6...145 psi: -0.1...1 MPa
Process connectionthreaded connection G 1/4 Internal thread (DIN EN ISO 1179-2)
Special featuregold-plated contacts
Measuring elementceramic-capacitive pressure measuring cell
Applicationfor industrial applications
Medialiquids and gases
Medium temperature [°C]-25...80
Min. burst pressure150 bar: 2175 psi: 15 MPa
Pressure rating75 bar: 1087 psi: 7.5 MPa
Vacuum resistance-1000 mbar: -0.1 MPa
Type of pressurerelative pressure; vacuum
Напряжение питания18...30 DC; (to SELV/PELV)
Current consumption [mA]< 35
Min. insulation resistance [MΩ]100; (500 V DC)
Protection classIII
Reverse polarity protectionyes
Power-on delay time [s]0.3
Integrated watchdogyes
Total number of outputs2
Output signalswitching signal; analog signal; IO-Link; (configurable)
Electrical designPNP/NPN
Number of digital outputs2
Output functionnormally open / closed; (configurable)
Напряжение питания2
Permanent current rating of switching output DC [mA]250
Switching frequency DC [Hz]< 500
Number of analog outputs1
Analog current output [mA]4...20; (scalable 1:5)
Max. load [Ω]500
Напряжение питания0...10; (scalable 1:5)
Min. load resistance [Ω]2000
Short-circuit protectionyes
Type of short-circuit protectionyes (non-latching)
Overload protectionyes
Analog start point-1...8 bar: -14.6...116 psi: -0.1...0.8 MPa
Analog end point1...10 bar: 14.6...145 psi: 0.1...1 MPa
Set point SP-0.94...10 bar: -13.6...145 psi: -0.094...1 MPa
Reset point rP-0.98...9.96 bar: -14.2...144.4 psi: -0.098...0.996 MPa
Min. difference between SP and rP0.05 bar: 0.6 psi: 0.005 MPa
In steps of0.01 bar: 0.1 psi: 0.001 MPa
Switch point accuracy [% of the span]< ± 0,4; (Turn down 1:1)
Repeatability [% of the span]< ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1)
Characteristics deviation [% of the span]< ± 0,25 (BFSL) / < ± 0,5 (LS); (Turn down 1:1; BFSL = Best Fit Straight Line; LS = limit value setting)
Hysteresis deviation [% of the span]< ± 0,1; (Turn down 1:1)
Long-term stability [% of the span]< ± 0,05; (Turn down 1:1; per 6 months)
Temperature coefficient zero point [% of the span / 10 K]< ± 0,2; (-0...80 °C)
Temperature coefficient span [% of the span / 10 K]< ± 0,2; (-0...80 °C)
Notes on the accuracy / deviationswitch point accuracy, linearity error under DNV GL: < ± 1%: < ± 1%
Время отклика< 1.5
Delay time programmable dS, dr [s]0...50
Damping process value dAP [s]0...4
Damping for the analog output dAA [s]0...4
Время отклика3
Parameter setting optionshysteresis / window; normally open / closed; switch-on/switch-off delay; Damping; Display unit; current/voltage output
Communication interfaceIO-Link
Transmission typeCOM2 (38,4 kBaud)
IO-Link revision1.1
SDCI standardIEC 61131-9
SIO modeyes
Required master port classA; (when pin 2 not connected: B)
Supported DeviceIDsType of operation: DeviceID; Factory setting / CMPT = 2: 463; Status_B High Resolution / CMPT = 3: 974
NoteFor further information please see the IODD PDF file at "Downloads"
ProfilesSmart Sensor - SSP 3.1: Measuring Sensor; Common - I&D: Identification and Diagnosis
Min. process cycle time [ms]3
IO-Link resolution pressure [bar]0.005
IO-Link process data (cyclical)Function: bit length; pressure: 16; device status: 4; binary switching information: 2
IO-Link functions (acyclical)application specific tag
Рабочая температура-25...80
Storage temperature [°C]-40...100
ProtectionIP 65; IP 67
EMCDIN EN 61000-6-2; DIN EN 61000-6-3
Shock resistanceDIN EN 60068-2-27: 50 g (11 ms)
Vibration resistanceDIN EN 60068-2-6: 20 g (10...2000 Hz)
MTTF [years]138
UL approvalUL approval number: J012
Pressure equipment directivesound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Масса239
Housingtubular
Dimensions [mm]Ø 34 / L = 90.7
Материалstainless steel (1.4404 / 316L); PBT+PC-GF30; PBT-GF20; PC
Материалstainless steel (1.4404 / 316L); Al2O3 (ceramics); FKM
Min. pressure cycles100 million
Tightening torque [Nm]25...35; (recommended tightening torque; Depends on lubrication, seal and pressure rating)
Restrictor element integratedno (can be retrofitted)
DisplayDisplay unit: 3 x LED, green (bar, psi, MPa); Switching status: 2 x LED, yellow; Measured values: alphanumeric display, red/green 4-digit
Pack quantity1 pcs.
Connector1 x M12; coding: A; Contacts: 4, gold-plated
Получить предложение по этой позиции