ifm electronic gmbh SL0105
Airflow monitor, SLG23CEEAKOA/6M/PH
Категории:
Технические характеристики
| Number of inputs and outputs | Number of relay outputs: 1 |
|---|---|
| Process connection | Clamp fitting Ø 23 mm |
| Medium temperature [°C] | -10...50 |
| Pressure rating | 1 bar: 0.1 MPa |
| Напряжение питания | 80...250 AC / 90...250 DC |
| Max. power consumption [VA] | 3 |
| Min. insulation resistance [MΩ] | 100; (500 V DC) |
| Reverse polarity protection | no |
| Power-on delay time [s] | 60 |
| Output signal | switching signal |
| Number of relay outputs | 1 |
| Contact rating | 3 A (30 V DC / 250 V AC) |
| Switching function flow monitoring | relay energized when flow is present |
| Short-circuit proof | no |
| Overload protection | no |
| Setting range [cm/s] | 100...1000 |
| Greatest sensitivity [cm/s] | 100...400 |
| Max. temperature gradient of medium [K/min] | 5 |
| Время отклика | 3...60 |
| Adjustment of the switch point | potentiometer |
| Рабочая температура | -10...50 |
| Storage temperature [°C] | -25...85 |
| Max. relative air humidity [%] | 90 |
| Protection | IP 65 |
| MTTF [years] | 747 |
| Масса | 386 |
| Housing | tubular |
| Dimensions [mm] | Ø 23 / L = 142 |
| Материал | housing: PBT; sensor surface: titanium |
| Материал | PBT; titanium |
| Display | Function: 1 x LED, red; Function: 1 x LED, green |
| Required protection | miniature fuse to IEC60127-2 sheet 1; ≤ 5 A; fast acting |
| Items supplied | Mounting clamp: 1, E40048 |
| Remarks | Recommendation Check the safe functioning of the unit after a short circuit. |
| Pack quantity | 1 pcs. |
| Cable | 6 m, PUR; 4 x 0.5 mm², PVC |