SMF221

ifm electronic gmbh SMF221

Magnetic-inductive flow meter, SMG25KGFFRKG/USD

  • Бренд: ifm electronic gmbh
  • Артикул (MPN): SMF221
  • Статус производства: Не определён

Категории:

Технические характеристики

Measuring range-20...150 °C: -4...302 °F
Nominal diameterDN25 (1“)
Process connectionifm-specific device flange
Special featuregold-plated contacts
Applicationfood and beverage industry
MediaConductive liquids; water; water-based media
Note on mediafood products such as beer, milk, fruit juices, soft drinks, ketchup, yogurt, yogurt toppings, ice cream; conductivity: ≥ 5 µS/cm
Medium temperature-20...150 °C: -4...302 °F
Min. burst pressure870 psi: 6 MPa
Pressure rating580.1 psi: 4 MPa
Напряжение питания18...32 DC
Current consumption [mA]250; (24 V)
Protection classIII
Reverse polarity protectionyes
Power-on delay time [s]< 5
Measuring principlemagnetic-inductive
Total number of inputs and outputs2
InputsOUT2: external totalizer reset
Total number of outputs2
Output signalOUT1: pulse signal; totalizer switching signal; diagnostic signal; IO-Link; OUT2: analog signal; pulse signal; totalizer switching signal; diagnostic signal
Electrical designPNP/NPN
Pulse outputflow rate meter
Short-circuit protectionyes
Type of short-circuit protectionyes (non-latching)
Overload protectionyes
Number of analog outputs1
Analog current output [mA]4...20; (skalierbar)
Max. load [Ω]500
Resolution of analog output0.38 µA
Number of digital outputs2
Напряжение питания2
Permanent current rating of switching output DC [mA]100
Switching frequency DC [Hz]0...10000
Display range-20...150 °C: -4...302 °F
Resolution0.01 °C: 0.1 °F
Note on factory setting0…20 gpm
Analog start point ASP-300...240 l/min: -18000...14400 l/h: -79.25...63.4 gpm: -33.41...26.73 ft/s
Analog end point AEP-240...300 l/min: -14400...18000 l/h: -63.4...79.25 gpm: -26.73...33.41 ft/s
Low flow cut-off LFC0...240 l/min: 0...14400 l/h: 0...63.4 gpm: 0...26.73 ft/s
Pulse length [s]0.00005...2
Pulse value0.004...99990000 I
Analog start point-20...116 °C: -4...240.8 °F
Analog end point14...150 °C: 57.2...302 °F
Measuring range [µS/cm]100...100000
Display range [µS/cm]0...10000000
Resolution [µS/cm]1
Analog start point [µS/cm]0...80000
Analog end point [µS/cm]20000...100000
Accuracy (in the measuring range)in the range of 100...20000 µS/cm: ±10% MW; in the range of 20000...100000 µS/cm: ±20% MW
Repeatability± 5% MW
Accuracy [K]± 1 (v > 0,5 m/s)
Repeatability [K]± 0,5 (v > 0,5 m/s)
Время отклика< 2
Damping process value dAP [s]0...5
Diagnostic functionsdirection of flow detection; liquid detection
Communication interfaceIO-Link
Transmission typeCOM3 (230,4 kBaud)
IO-Link revision1.1.3
SDCI standardIEC 61131-9
ProfilesSmart Sensor - SSP 4.3.4: Measuring and Switching Sensor, floating point, 4 channel; BLOB: Binary Large Object transfer; Common - I&D: Identification and Diagnosis; Extension: Sensor Control Wide; Extension: Quantity detection, switches when value exceeds the setpoint; Function: Locator; Function: ProductURI
SIO modeyes
Required master port classA
Process data analog6
Process data binary8
Min. process cycle time [ms]1.9
IO-Link process data (cyclical)Function: bit length; totalizer: 32; flow: 32; temperature: 32; conductivity: 32; status: 4; binary switching information: 8
IO-Link functions (acyclical)direction of flow detection; totalizer; memory; operating hours counter; internal temperature; simulation function
Supported DeviceIDsType of operation: DeviceID; default: 1787
Рабочая температура-20...65 °C: -4...149 °F
Storage temperature-20...80 °C: -4...176 °F
ProtectionIP 67; IP 69; (to DIN EN 60529)
EMCDIN 61326-1
Shock resistanceDIN IEC 68-2-27: 20 g (18ms)
Vibration resistanceDIN IEC 68-2-6: 5 g (10...2000Hz)
MTTF [years]81
UL approvalUL approval number: I031; File number UL: E174189
Pressure equipment directivesound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Масса3695.6
Housingtubular
Inlet pipe length5 x DN
Outlet pipe length2 x DN
Dimensions [mm]Ø 114.3 / L = 86
Материалhousing: stainless steel (1.4404 / 316L); flange: stainless steel (1.4301 / 304); electronics fixture: stainless steel (1.4301 / 304); electronics: stainless steel (1.4404 / 316L); Display: polysulfone; Display-sealing: FKM; LED ring: PP
МатериалPipe section: PFA; electrodes: stainless steel (1.4435 / 316L)
Surface characteristics Ra/Rz of the wetted partsRa < 0.4 μm
Displayprocess value: full graphics TFT display, multi-color 3,5" 128 x 128 Pixel; display layouts: 4; display rotation: 4 x 90°; operating status: LED ring, three-color
Display unitl/min; l/h; hl/min; hl/h; m³/min; m³/h; m/s; gpm; gph; ft/s; °C; °F; μS/cm; S/m; ms/cm
Factory settinggpm; °F; μS/cm
LanguageGerman; English; Spanish; French; Italian; Japanese; Korean; Portuguese; Chinese
Operating elements4: capacitive pushbuttons
RemarksMW = Measured value; MEW = Final value of the measuring range; pulse and totalizer signal are only available for one of the two outputs; reference conditions (1/2): water (free of gas bubbles), 15...35 °C, process connection: DIN32676 series A, pipe standard suitable for process connection; reference conditions (2/2): inlet pipe length 10xDN, outlet pipe length 5xDN, device settling time: 30 minutes, device orientation: horizontal, display orientation: up; accuracy specifications according to factory certificate on delivery
NotesFür die Inbetriebnahme des Sensors werden zusätzlich ein passender Prozessadapter und eine Dichtung benötigt.; Die passenden Produkte finden Sie im Zubehör.
Pack quantity1 pcs.
Connector1 x M12; coding: A; Contacts: 4, gold-plated
Получить предложение по этой позиции