ifm electronic gmbh SUC300
Ultrasonic flow meter, SUO50IGAFRKG/US
Технические характеристики
| Measuring range | 20...1000 l/min: 1200...60000 l/h: 1.2...60 m³/h |
|---|---|
| Nominal diameter | DN40 (1 1/2"); DN50 (2") |
| Process connection | clamp-on |
| Special feature | gold-plated contacts |
| Application | Use in industrial applications |
| Media | ultra-pure water; water; water-based media |
| Note on media | water-based media: for media with >10 % additives, the repeatability is the only available value |
| Medium temperature [°C] | -20...100 |
| Материал | metal: steel; stainless steel, copper; plastics: PVC; CPVC; PP |
| Outer diameter [mm] | 44...64 |
| Wall thickness [mm] | 0,1...11,1 |
| Напряжение питания | 18...32 DC; (to SELV/PELV) |
| Current consumption [mA] | < 75 |
| Protection class | III |
| Reverse polarity protection | yes |
| Power-on delay time [s] | 5 |
| Measuring principle | ultrasonic |
| Total number of inputs and outputs | 2 |
| Inputs | OUT2: counter reset |
| Total number of outputs | 2 |
| Output signal | OUT1: switching signal; pulse signal; diagnostic signal; totalizer switching signal; frequency signal; IO-Link; OUT2: switching signal; pulse signal; diagnostic signal; totalizer switching signal; analog signal |
| Electrical design | PNP/NPN |
| Pulse output | flow rate meter |
| Short-circuit protection | yes |
| Type of short-circuit protection | yes (non-latching) |
| Overload protection | yes |
| Number of analog outputs | 1 |
| Analog current output [mA] | 4...20 |
| Max. load [Ω] | 500 |
| Number of digital outputs | 2 |
| Output function | normally open / closed; (configurable) |
| Напряжение питания | 2 |
| Permanent current rating of switching output DC [mA] | 100 |
| Switching frequency DC [Hz] | 0...10000 |
| Display range | 0...1200 l/min: 0...72000 l/h: 0...72 m³/h |
| Resolution | 0.1 l/min: 1 l/h: 0.001 m³/h |
| Set point SP | 25.5...1000 l/min: 1530...60000 l/h: 1.53...60 m³/h |
| Reset point rP | 20.3...994.8 l/min: 1220...59690 l/h: 1.22...59.69 m³/h |
| Analog start point ASP | -1000...800 l/min: -60000...48000 l/h: -60...48 m³/h |
| Analog end point AEP | -800...1000 l/min: -48000...60000 l/h: -48...60 m³/h |
| Low flow cut-off LFC | 20...50 l/min: 1200...3000 l/h: 1.2...3 m³/h |
| Frequency end point, FEP | 200.6...1000 l/min: 12037...60000 l/h: 12.04...60 m³/h |
| Frequency at the end point FRP [Hz] | 1...10000 |
| Measuring range [°C] | -20...100 |
| Display range [°C] | -44...124 |
| Resolution [°C] | 0.1 |
| Set point SP [°C] | -19.6...100 |
| Reset point rP [°C] | -20...99.6 |
| Analog start point [°C] | -20...76 |
| Analog end point [°C] | 4...100 |
| Frequency start point, FSP [°C] | -20...76 |
| Frequency end point, FEP [°C] | 4...100 |
| Pulse length [s] | 0.002...2 |
| Pulse value | 0.1...99990000 I |
| Accuracy (in the measuring range) | water "reference conditions": ± (2,0 % MW + 0,5 % MEW); water: ± (5,0 % MW + 0,5 % MEW) |
| Repeatability | ± 0,2 % MEW |
| Accuracy [K] | temperature reference conditions: ± 5 (Q > 5 % MEW) |
| Temperature coefficient [% of the span / 10 K] | 0,2 |
| Время отклика | < 0.25; (dAP = 0, T09) |
| Damping process value dAP [s] | 0...5 |
| Dynamic response T05 / T09 [s] | 62 / 263 |
| Diagnostic functions | direction of flow detection; signal quality |
| Communication interface | IO-Link |
| Transmission type | COM2 (38,4 kBaud) |
| IO-Link revision | 1.1 |
| SDCI standard | IEC 61131-9 |
| Profiles | BLOB: Binary Large Object transfer; Common - I&D: Identification and Diagnosis; Function: Locator; Function: ProductURI |
| Required master port class | A |
| Process data analog | 3 |
| Process data binary | 2 |
| Min. process cycle time [ms] | 9.6 |
| IO-Link process data (cyclical) | Function: bit length; totalizer: 32; Flow monitoring: 32; Temperature monitoring: 32; status: 4; Output 1: 1; Output 2: 1 |
| Supported DeviceIDs | Type of operation: DeviceID; default: 2001 |
| Рабочая температура | -20...60 |
| Storage temperature [°C] | -25...80 |
| Max. relative air humidity [%] | 90; (non condensing) |
| Protection | IP 67; IP 69; (DIN EN 60529) |
| EMC | DIN 61326-1:2021 |
| Shock resistance | DIN IEC 68-2-27: 20 g (11ms) |
| Vibration resistance | DIN IEC 68-2-6: 20 g (10...2000Hz) |
| MTTF [years] | 160 |
| UL approval | UL approval number: I040; File number UL: E174189 |
| Масса | 658 |
| Housing | rectangular |
| Inlet pipe length | 10 x DN |
| Outlet pipe length | 5 x DN |
| Dimensions [mm] | 101.9 x 88 x 123.1 |
| Материал | housing: stainless steel (1.4404 / 316L); clamp: stainless steel (17-4 PH/1.4542); Display: PFA; sealing Display: FKM; connector: PBT; couplant: EPDM |
| Display | Color display 1,44", 128 x 128 pixels; Switching function: 2 x LED, yellow; diagnosis: 1 x LED, three-color |
| Display unit | l/min; l/h; m³/h; °C |
| Factory setting | l/min; °C |
| Language | German; English; Spanish; French; Italian; Japanese; Korean; Portuguese; Chinese |
| Items supplied | couplant, E33911 |
| Remarks | MW = Measured value; MEW = Final value of the measuring range; pulse and totalizer signal are only available for one of the two outputs; Installation on a clean pipe (avoid rust, frost and condensation on the surface and weld seams).; to achieve a measurement accuracy of 2 %, the specified reference conditions must be observed:; medium water free of gas bubbles, temperature 25°C, nominal diameter DN50 (2"), pipe material stainless steel; Accuracy is achieved with optimized setup:; •90% water-based media; • Pipe material is correctly selected; •Outer diameter is entered correctly within +/- 0.1mm; • Wall thickness is automatically measured or accurately entered |
| Pack quantity | 1 pcs. |
| Connector | 1 x M12; coding: A; Contacts: 4, gold-plated |