Технические характеристики
| Process connection | threaded connection M22 x 1,5 external thread |
|---|---|
| Measuring range [l/min] | 0...50 |
| Special feature | gold-plated contacts |
| Application | Industrial applications; Cooling water control |
| Installation | connection to pipe by means of an adapter; tube connection |
| Measuring parameters | flow; temperature; pressure; totalizer |
| Control | manual |
| Media | water; glycol solutions |
| Medium temperature [°C] | -10...80 |
| Pressure rating [bar] | 10 |
| Components | SU ultrasonic flowmeters for water and oil based media, SU7200; Electronic pressure monitor, PN7594; filter; water stop valve; regulating valve; backstop; Cover plate |
| Output signal | switching signal |
| Output function | normally open / closed; (configurable) |
| Measuring range [bar] | 0...10 |
| Measuring range [°C] | -10...80 |
| Рабочая температура | -10...50 |
| Storage temperature [°C] | -25...80 |
| Protection | IP 65; (sensors) |
| EMC | DIN EN 61000-6-2; DIN EN 61000-6-3 |
| Pressure equipment directive | sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
| Масса | 7781.2 |
| Type of mounting | mounting bracket with protective cover |
| Dimensions [mm] | 500 x 218 x 150 |
| Материал | stainless steel (1.4404 / 316L); PBT-GF20; PC; FKM; PBT+PC-GF30; bronze (2.1096.01); Aluminum Alloy anodized AlMgSi0,5; PA |
| Материал | stainless steel (1.4404 / 316L); FKM; PES; NBR; PVDF; Centellen 200; ceramics |
| Pack quantity | 1 pcs. |
| Connector | 3 x M12; Contacts: gold-plated |