KE

KEYENCE CORPORATION KV-TF40

KV-8000 series (Programmable Logic Controller) - KV-TF40

Категории:

Технические характеристики

TypeTemperature control unit
Memory elementsEEPROM rewritable one million times
Number of temperature input points4 ch
InputThermocoupler/Platinum temperature measuring resistor
Temperature sensor typesThermocoupler: K, J, T, E, R, B, N, S, W5Re/W26Re Platinum temperature measuring resistor: JPt100, Pt100
Indicated accuracy±0.3% of F.S. ±1 digit (at 25°C 77°F ), ±0.7% of F.S. ±1 digit (at 0 to 50°C 32 to 122°F )
Cold junction correction precision±1°C ±1.8°F
Sampling cycle125 ms/ch (500 ms/4 ch)
Control period1 to 100 seconds
Operation modePID control (with auto-tuning and 3 mode stabilizer function installed), Heat/cool PID control (with auto-tuning and 3 mode stabilizer function installed), ON/OFF control
Tuning modePID auto-tuning mode
Control outputTransistor (sink)
Alarm outputTransistor (sink)
Alarm modeAbsolute value upper limit, absolute value lower limit, deviation upper limit, deviation lower limit, deviation upper limit unexcited, deviation lower limit unexcited, deviation upper and lower limits, within upper and lower limit deviation, absolute value upper limit unexcited, absolute value lower limit unexcited
Output (Rated load)30 VDC, 100 mA or less
Output (Leakage current at OFF)100 μA or less
Напряжение питания1.5 V or less
Current sensor (CT) input4 ch
Current measurement precisionLarger of ±5% of an input value and ±2 A of an input value
Insulation modeBetween inputs and outputs: Photocoupler and transformer insulation, Between input channels: Photocoupler and transformer insulation
OthersHeater wire breaking alarm, control loop wire breaking alarm, measured value bias, output limit, slope setup, manual reset, output control when an error occurs
Internal current consumption210 mA or less
МассаApprox. 270 g
Запросить КП по этой позиции