KE

KEYENCE CORPORATION MP-FEA1

MP-F series (Air Quality Multi-Sensor) - MP-FEA1

  • Бренд: KEYENCE CORPORATION
  • Артикул (MPN): MP-FEA1
  • Серия: MP-F Series
  • Статус производства: В производстве

Категории:

Технические характеристики

Measurement specifications (Electrical service type)1-phase 2-wire, 1-phase 3-wire, 3-phase 3-wire, 3-phase 4-wire (switchable)
Measurement specifications (Number of measurement circuits)1 (up to 2 circuits with the 1-phase 2-wire setting )
Input specifications (Primary-side rated current, In)When using specialized CT MP-FEC100: 100 A Or, general CT (secondary-side rated input current 1 A) When using specialized CT MP-FEC250: 250 A Or, general CT (secondary-side rated input current 1 A) When using specialized CT MP-FEC600: 600 A Or, general CT (secondary-side rated input current 1 A) When using specialized CT MP-FEC50M: 50 A When using specialized CT MP-FEC100M: 100 A
Input specifications (Over current withstand capability)1.2 times the primary-side rated current (can be applied consecutively), 10 times the primary-side rated current (for 1 second or less)
Напряжение питания・MP-FEC100/MP-FEC250/MP-FEC600, or general CT in use: 100 to 277 VAC (L-N) ・MP-FEC50M/MP-FEC100M in use: 100 to 240 VAC (L-N); ・MP-FEC100/MP-FEC250/MP-FEC600, or general CT in use: 100 to 240 VAC (L-N), 200 to 480 VAC (L-L) ・MP-FEC50M/MP-FEC100M in use: 100 to 240 VAC (L-N), 200 to 480 VAC (L-L); ・MP-FEC100/MP-FEC250/MP-FEC600, or general CT in use: 173 to 480 VAC (L-L) ・MP-FEC50M/MP-FEC100M in use: 173 to 240 VAC (L-L); ・MP-FEC100/MP-FEC250/MP-FEC600, or general CT in use: 100 to 277 VAC (L-N), 173 to 480 VAC (L-L) ・MP-FEC50M/MP-FEC100M in use: 100 to 240 VAC (L-N), 173 to 415 VAC (L-L)
Напряжение питания・MP-FEC100/MP-FEC250/MP-FEC600, or general CT in use: 480 VAC to earth ・MP-FEC50M/MP-FEC100M in use: 240 VAC to earth
Напряжение питания−15% to +15% of the rated input voltage
Input specifications (Rated input frequency)50/60 Hz
Напряжение питанияDisplay resolution 0.1 [V]
Displayable range/ Display resolution (Main Unit) (Current)Display resolution 0.001 [A]
Displayable range/ Display resolution (Main Unit) (Active power/reactive power/apparent power)-8942.400 to +8942.400 [kW/kvar/kVA], display resolution 0.001 [kW/kvar/kVA]
Displayable range/ Display resolution (Main Unit) (Active energy/reactive energy/apparent energy)0.000 to 999999.999 [kWh/kvarh/kVAh], display resolution 0.001 [kWh/kvarh/kVAh]
Displayable range/ Display resolution (Main Unit) (Power factor (PF))-1.00 to 1.00, display resolution 0.01
Displayable range/ Display resolution (Main Unit) (Frequency)0.0 to 90.0 [Hz], display resolution 0.1 [Hz]
Напряжение питания±0.5% of RD (within rated input voltage)
Measurement accuracy (Current)・MP-FEC100/MP-FEC250/MP-FEC600, or general CT in use: ±0.5% of RD (5% ≤ In ≤ 120%), ±1.0% of RD (1% ≤ In ・MP-FEC50M/MP-FEC100M in use: ±0.5% of F.S.
Measurement accuracy (Active energy)・MP-FEC100/MP-FEC250/MP-FEC600, or general CT in use: Compliant with IEC 62053-22 §7.9 table 3 class 0.5 Power factor 1: ±0.5% of RD (5% ≤ In ≤ 120%), ±1.0% of RD (1% ≤ In Power factor 0.5 inductive: ±0.6% of RD (10% ≤ In ≤ 120%), ±1.0% of RD (2% ≤ In Power factor 0.8 capacitive: ±0.6% of RD (10% ≤ In ≤ 120%), ±1.0% of RD (2% ≤ In ・MP-FEC50M/MP-FEC100M in use: ±1.0% of RD (1% ≤ In ≤ 120%)
Measurement accuracy (Reactive energy)・MP-FEC100/MP-FEC250/MP-FEC600, or general CT in use: Compliant with IEC 62053-23 §7.9 table 3 class 2 Reactive power factor 1: ±2.0% of RD (5% ≤ In ≤ 120%), ±2.5% of RD (1% ≤ In Reactive power factor 0.5 inductive or capacitive: ±2.0% of RD (10% ≤ In ≤ 120%), ±2.5% of RD (5% ≤ In Reactive power factor 0.25 inductive or capacitive: ±2.5% of RD (10% ≤ In ≤ 120%) ・MP-FEC50M/MP-FEC100M in use: ±2.0% of RD (5% ≤ In ≤ 120%)
Measurement accuracy (Apparent energy)・MP-FEC100/MP-FEC250/MP-FEC600, or general CT in use: ±0.5% of RD (5% ≤ In ≤ 120%), ±1.0% of RD (1% ≤ In ・MP-FEC50M/MP-FEC100M in use: ±1.0% of RD (5% ≤ In ≤ 120%)
Рабочая температура±0.03%/K
Measurement accuracy (Effect of harmonics)±0.5% of RD
Measurement accuracy (Power factor (PF))±0.01
Measurement accuracy (Power)±0.1 [Hz]
Current consumption36 mA
Напряжение питанияAcross all terminals and housing: 2500 VAC for 1 minute Across voltage measurement terminal and communication terminal: 2500 VAC for 1 minute Across CT input terminal and communication terminal (When using a specialized CT): 2500 V for 1 minute
Insulation resistanceAcross all terminals and housing: 20 MΩ min. (500 VDC) Across voltage measurement terminal and CT input terminal and across communication terminal: 20 MΩ min. (500 VDC)
Рабочая температура-5 to +55°C 23 to 131°F (no freezing)
Environmental resistance (Relative humidity)35%RH to 85%RH (no condensation)
Environmental resistance (Measurement category)II
Environmental resistance (Altitude)2500 m or less
Environmental resistance (Pollution degree)2
Environmental resistance (Mounting method)DIN rail mounting
Environmental resistance (Vibration resistance)10 to 500 Hz, power spectral concentration: 0.033G 2 /Hz, XYZ axes
Environmental resistance (Shock resistance)150 m/s 2 , 2 times each for X, Y, and Z axes
МатериалPolycarbonate
МассаApprox. 110 g 3.88 oz
Запросить КП по этой позиции