EMU4-LG1-MB

Mitsubishi Electric Corporation (Factory Automation / FA Systems Group) EMU4-LG1-MB

EMU4-LG1-MB

Технические характеристики

CategoryEnergy Saving Supporting Devices
GroupEnergy Measuring Unit
ModelEcoMonitorPlus
UseInsulation Monitor Model
TransmissionMODBUS RTU (RS-485) communication
Phase wire systemSingle-phase 2-wire, single-phase 3-wire, 3-phase 3-wire, 3-phase 4-wire common
Single-phase 2-wire 3-phase 3-wire110V, 220V, 440V AC common
Single-phase 3-wire110V AC (between wires 1 and 2, and wires 2 and 3), 220V AC (between wires 1 and 3) 220V AC (between wires 1 and 2, and wires 2 and 3), 440V AC (between wires 1 and 3)
3-phase 4-wireMinimum: 63.5V/110V AC, Maximum: 277V/480V AC
Current circuit1A (Mitsubishi ZCT is used. Primary current value of ZCT is indicated.)
Frequency50/60Hz (automatic frequency selection)
Auxiliary power rating100V-240V AC (+10%, -15%) 50Hz/60Hz
No. of measurement circuits1 circuit
Напряжение питанияFor each phase: 0.1VA (110V AC), 0.2VA (220V AC), 0.4VA (440V AC)
Auxiliary power circuit110V AC: 2.0VA, 220V AC: 3.0VA
Measurement itemsLeakage current, demanded leakage current, resistance leakage current, demanded resistance leakage current, resistance leakage current difference conversion value
Main unit tolerancesLow sensitivity mode Leakage current Io, resistive leakage current Ior: ±2.5% (relative to 10 to 100% of rating) Leakage current Io, resistive leakage current Ior: ±2.5 mA (relative to 10% of rating or lower) High sensitivity mode Leakage current Io, resistive leakage current Ior: ±2.5 mA
Data update cycleLeakage current: 2 sec, resistive leakage current: 2 sec
Output signal formatNon-voltage a-contact, 1 output
Compatible standardCE marking (EMC: EN-61326-1: 2013, Safety: EN-61010-1: 2010), UL: UL61010-1
Масса0.2kg
External dimensions (unit: mm)37.5 (W) x 90 (H) x 92.9 (D) (excluding protruding parts) (Maximum size including projections: 41.5 (W) x 99 (H) x 94 (D))
Category (site listing)EcoMonitorPlus