FX1N-40MR

Mitsubishi Electric Corporation (Factory Automation / FA Systems Group) FX1N-40MR

FX1N-40MR

Технические характеристики

Operation control systemStored program repetitive operation system with interruption function
Input/output control systemBatch processing system (when END instruction is executed), Input/output refresh instruction and pulse catch function are provided.
Programming languageRelay symbol system + step-ladder system (SFC notation possible)
Max. memory capacity8000 steps Up to 8000 steps, including comment and file registers
Built-in memory capacity/type8000 EEPROM (memory backup not required)
Memory cassette (Memory board)FX1N-EEPROM-8L (8000 steps EEPROM)
Writing function during runningProvided (Program can be modified while the PLC is running.)
ProtectionPassword protection provided (with entry code function)
Clock functionBuilt-in 1980 to 2079 (with correction for leap year), 2- or 4-digit year, accuracy within ±45 seconds/month at 25°C *Precaution for clock function The current time of the built-in clock is backed up by a high-capacity capacitor (built-in). The large-capacity capacitor (built-in) fully charges in 30 minutes and retains the current value for ten days. The optional battery can also be used to hold the time.
Basic instructions・Sequence instructions: 27 ・Step-ladder instructions: 2
Applied instructionsApplied instructions: 89 kinds
Processing speed > Basic instructions0.55 to 0.7 μs/instruction
Processing speed > Applied instructions3.7 μs to several hundred μs/instruction
No. of input points24 points
No. of output points16 points
Remote I/O number of points (CC-Link)128 points or less including mounted I/O
Total number of points128 points or less (Extension combined number)
Input relayX000 to X177 128 points (octal) Extension-combined
Output relayY000 to Y177 128 points (octal) Extension-combined
For generalM0 to M383 384 points
For keeping (EEPROM keep)M384 to M511 128 points *Precaution for keeping area The keeping area and non-keeping area are fixed. (Cannot be changed with parameter) The PLC power must be on for at least 5 minutes to accurately keep the data in the EEPROM.
For keeping (capacitor keeping)M512 to M1535 1024 points *Precaution for keeping area The keeping area and non-keeping area are fixed. (Cannot be changed with parameter) The large-capacity capacitor (built-in) fully charges in 30 minutes and retains the current value for ten days. The capacitor keeping device may not hold its state correctly if the large-capacity capacitor’s voltage is low. When using the FX1N series PLC for the first time after purchase or after a long period of no power supply, initialize the capacitor keeping device. Before resuming operation, set the devices and the current time required for operation.
For specialM8000 to M8255 256 points
Initial state (EEPROM keep)S0 to S9 10 points *Precaution for keeping area The keeping area and non-keeping area are fixed. (Cannot be changed with parameter) The PLC power must be on for at least 5 minutes to accurately keep the data in the EEPROM.
Device > State > For keeping (EEPROM keep)S10 to S127 118 points * Precaution for keeping area The keeping area and non-keeping area are fixed. (Cannot be changed with parameter) The PLC power must be on for at least 5 minutes to accurately keep the data in the EEPROM.
Device > State > For keeping (capacitor keeping)S128 to S999 872 points *Precaution for keeping area The keeping area and non-keeping area are fixed. (Cannot be changed with parameter) The large-capacity capacitor (built-in) fully charges in 30 minutes and retains the current value for ten days. The capacitor keeping device may not hold its state correctly if the large-capacity capacitor’s voltage is low. When using the FX1N series PLC for the first time after purchase or after a long period of no power supply, initialize the capacitor keeping device. Before resuming operation, set the devices and the current time required for operation.
100 msT0 to T199 200 points (0.1 to 3,276.7 sec)
10 msT200 to T245: 46 points (0.01 to 327.67 sec)
1 ms accumulating type (capacitor keep)T246 to T249 4 points (0.001 to 32.767 sec) *Precaution for keeping area The keeping area and non-keeping area are fixed. (Cannot be changed with parameter) The large-capacity capacitor (built-in) fully charges in 30 minutes and retains the current value for ten days. The capacitor keeping device may not hold its state correctly if the large-capacity capacitor’s voltage is low. When using the FX1N series PLC for the first time after purchase or after a long period of no power supply, initialize the capacitor keeping device. Before resuming operation, set the devices and the current time required for operation.
100 ms accumulating type (capacitor keep)T250 to T255 6 points (0.1 to 3,276.7 sec) *Precaution for keeping area The keeping area and non-keeping area are fixed. (Cannot be changed with parameter) The large-capacity capacitor (built-in) fully charges in 30 minutes and retains the current value for ten days. The capacitor keeping device may not hold its state correctly if the large-capacity capacitor’s voltage is low. When using the FX1N series PLC for the first time after purchase or after a long period of no power supply, initialize the capacitor keeping device. Before resuming operation, set the devices and the current time required for operation.
OthersAvailable as analog timers VR1: D8030, VR2: D8031 2 points (0 to 255)
16 bits upC0 to C15 16 points (Counting from 0 to 32,767)
16 bits up (EEPROM keep)C16 to C31 16 points (Counting from 0 to 32,767) *Precaution for keeping area The keeping area and non-keeping area are fixed. (Cannot be changed with parameter) The PLC power must be on for at least 5 minutes to accurately keep the data in the EEPROM.
16 bit up/down (capacitor keeping)C32 to C199 168 points (Counting from 0 to 32,767) *Precaution for keeping area The keeping area and non-keeping area are fixed. (Cannot be changed with parameter) The large-capacity capacitor (built-in) fully charges in 30 minutes and retains the current value for ten days. The capacitor keeping device may not hold its state correctly if the large-capacity capacitor’s voltage is low. When using the FX1N series PLC for the first time after purchase or after a long period of no power supply, initialize the capacitor keeping device. Before resuming operation, set the devices and the current time required for operation.
32 bits up or downC200 to C219 20 points (Counting from -2,147,483,648 to +2,147,483,647)
32 bit up/down (capacitor keeping)C220 to C234 15 points (Counting from -2,147,483,648 to +2,147,483,647) *Precaution for keeping area The keeping area and non-keeping area are fixed. (Cannot be changed with parameter) The large-capacity capacitor (built-in) fully charges in 30 minutes and retains the current value for ten days. The capacitor keeping device may not hold its state correctly if the large-capacity capacitor’s voltage is low. When using the FX1N series PLC for the first time after purchase or after a long period of no power supply, initialize the capacitor keeping device. Before resuming operation, set the devices and the current time required for operation.
High-speed counter[32 bits high-speed up/down (EEPROM keep)] C235 to C255 1-phase: 60 kHz, 10 kHz 2-phase: 30 kHz, 5 kHz The number of points that can be used and the input frequency are limited depending on the conditions of use. *Precaution for keeping area The keeping area and non-keeping area are fixed. (Cannot be changed with parameter) The PLC power must be on for at least 5 minutes to accurately keep the data in the EEPROM.
16 bits for generalD0 to D127 128 points
For 16 bits keep (EEPROM keep)D128 to D255 128 points *Precaution for keeping area The keeping area and non-keeping area are fixed. (Cannot be changed with parameter) The PLC power must be on for at least 5 minutes to accurately keep the data in the EEPROM.
16 bit for keeping (capacitor keeping)D256 to D7999 7744 points *Precaution for keeping area The keeping area and non-keeping area are fixed. (Cannot be changed with parameter) The large-capacity capacitor (built-in) fully charges in 30 minutes and retains the current value for ten days. The capacitor keeping device may not hold its state correctly if the large-capacity capacitor’s voltage is low. When using the FX1N series PLC for the first time after purchase or after a long period of no power supply, initialize the capacitor keeping device. Before resuming operation, set the devices and the current time required for operation.
File register (keep)D1000 to D7999 Maximum 7000 points (Can be set as file registers in units of 500 points from D1000 in the program area (EEPROM) using parameters.)
16 bits for specialD8000 to D8255 256 points
16 bits for indexV0 to V7, Z0 to Z7: 16 points
For branching of JUMP and CALLP0 to P127 128 points (For CJ instructions and CALL instructions, P63 jumps to END instruction)
Input interruptionI00□ to I50□: 6 points
Nesting[For master control] N0 to N7: 8 points (For MC instructions)
Decimal number (K)16 bits: -32,768 to +32,767 32 bits: -2,147,483,648 to +2,147,483,647
Hexadecimal number (H)16 bits: 0 to FFFF 32 bits: 0 to FFFFFFFF
Напряжение питания100 to 240 V AC
Напряжение питания85 to 264 V AC
Frequency rating50/60 Hz
Allowable instantaneous power failure timeOperation can be continued upon occurrence of instantaneous power failure for 10 ms or less.
Power fuse250 V 3.15 A
Rush current30 A max. 5 ms or less/100 V AC, 50 A max. 5 ms or less/200 V AC
Power consumption32W Includes input current (7 or 5 mA per point)
24 V DC service power supply400 mA This is irrelevant for the connection of extension blocks.
Input connection typeRemovable terminal block (M3 screw)
Input typeSink
Напряжение питания24 V DC ±10%
X000 to X0073.3 kΩ
X010 or more4.3 kΩ
Input signal current > X000 to X0077 mA/24 V DC
Input signal current > X010 or more5 mA/24 V DC
ON input sensitivity current > X000 to X0074.5 mA or more
ON input sensitivity current > X010 or more3.5 mA or more
OFF input sensitivity current1.5 mA or less
Время откликаApprox. 10 ms X000 to X007 have built-in digital filters, which can be changed to 0 to 15 ms in 1 ms increments using the application D8020. When 0 is specified, X000 and X001 are 10 μs, and X002 to X017 are 50 μs.
Input signal formNo-voltage contact input NPN open collector transistor
Input circuit insulationPhotocoupler insulation
Indication of input operationLED is lit when input is on
Output connection typeTerminal block (M3 screw)
Output typeRelay output
External power supply250 V AC 30 V DC or less
Resistance load2 A or less/1 output point 8 A or less/COM terminal
Inductive load80 VA
Min. load5 V DC, 2 mA (reference value)
Open circuit leakage current-
Напряжение питания-
OFF→ONApprox. 10 ms
ON→OFFApprox. 10 ms
Insulation of circuitMechanical insulation
Indication of output operationWhen power is applied to relay coil, LED is lit.
1-phase 1-count input[C235, C236] Up to 2 points: Up to 60 kHz When used High-speed comparison SET/RESET: 30 kHz [C237 to C245] Up to 4 points: Up to 10 kHz When used High-speed comparison SET/RESET: 10 kHz The total frequency processed by the PLC with the high-speed counter and pulse density instruction (add double the input frequency when using a 2-phase counter) is a maximum of 60 kHz. When using the high-speed comparison SET/RESET, the total frequency processed by the PLC with the high-speed counter and pulse density instruction (add double the input frequency when using a 2-phase counter) is a maximum of 30 kHz.
1-phase 2-count input[C246] Up to 1 points: Up to 60 kHz When used High-speed comparison SET/RESET: 30 kHz [C247 to C250] Up to 2 points: Up to 10 kHz When used High-speed comparison SET/RESET: 10 kHz The total frequency processed by the PLC with the high-speed counter and pulse density instruction (add double the input frequency when using a 2-phase counter) is a maximum of 60 kHz. When using the high-speed comparison SET/RESET, the total frequency processed by the PLC with the high-speed counter and pulse density instruction (add double the input frequency when using a 2-phase counter) is a maximum of 30 kHz.
2-phase 2-count input[C251] Up to 1 point: Up to 30 kHz When used High-speed comparison SET/RESET: 15 kHz [C252 to C255] Up to 2 points: Up to 5 kHz When used High-speed comparison SET/RESET: 5 kHz The total frequency processed by the PLC with the high-speed counter and pulse density instruction (add double the input frequency when using a 2-phase counter) is a maximum of 60 kHz. When using the high-speed comparison SET/RESET, the total frequency processed by the PLC with the high-speed counter and pulse density instruction (add double the input frequency when using a 2-phase counter) is a maximum of 30 kHz.
Рабочая температура0 to 55°C (32 to 131°F) when operating and -20 to 70°C (-4 to 158°F) when stored
Ambient humidity35 to 85%RH (no condensation) when operating
Frequency: 10 to 57 HzHalf amplitude: 0.035mm Sweep Count for X, Y, Z: 10 times (80 min in each direction) The criterion is shown in IEC61131-2.
Frequency: 57 to 150 HzAcceleration: 4.9 m/s 2  Sweep Count for X, Y, Z: 10 times (80 min in each direction) The criterion is shown in IEC61131-2.
Vibration resistance > Direct installing > Frequency: 10 to 57 HzHalf amplitude: 0.075 mm Sweep Count for X, Y, Z: 10 times (80 min in each direction) The criterion is shown in IEC61131-2.
Vibration resistance > Direct installing > Frequency: 57 to 150 HzAcceleration: 9.8 m/s 2 Sweep Count for X, Y, Z: 10 times (80 min in each direction) The criterion is shown in IEC61131-2.
Shock resistance147 m/s 2 Acceleration, Action time: 11 ms, 3 times by half-sine pulse in each direction X, Y, and Z The criterion is shown in IEC61131-2.
Noise resistanceBy noise simulator at noise voltage of 1,000 Vp-p, noise width of 1 μs, rise time of 1 ns and period of 30 to 100 Hz
Напряжение питанияPerform dielectric withstand voltage test at the following voltage between each terminals and the main unit ground terminal. Between power supply terminal (AC power supply) and ground terminal: 1.5 kV AC for 1 min Between 24 V DC service power supply connected to input terminal (24 V DC) and ground terminal: 500 V AC for 1 min Between output terminal (relay) and ground terminal: 1.5 kV AC for 1 min
Insulation resistancePerform insulation resistance test at the following voltage between each terminals and the main unit ground terminal. Between power supply terminal (AC power supply) and ground terminal: 5 MΩ or higher by 500 V DC insulation resistance tester Between 24 V DC service power supply connected to input terminal (24 V DC) and ground terminal: 5 MΩ or higher by 500 V DC insulation resistance tester Between output terminal (relay) and ground terminal: 5 MΩ or higher by 500 V DC insulation resistance tester
GroundingClass D grounding (grounding resistance: 100 Ω or less) (Common grounding with a heavy electrical system is not allowed) Ground the PLC independently or jointly.
Working atmosphereFree from corrosive or flammable gas and excessive conductive dusts
Working altitude2000 m or less The PLC cannot be used at a pressure higher than the atmospheric pressure to avoid damage.
Category (site listing)Main unit