Mitsubishi Electric Corporation (Factory Automation / FA Systems Group) FX1S-10MR-D
FX1S-10MR-D
Технические характеристики
| Operation control system | Stored program repetitive operation system with interruption function |
|---|---|
| Input/output control system | Batch processing system (when END instruction is executed), Input/output refresh instruction and pulse catch function are provided. |
| Programming language | Relay symbol system + step-ladder system (SFC notation possible) |
| Max. memory capacity | 2000 steps Up to 2000 steps, including comment and file registers |
| Built-in memory capacity/type | 2000-step EEPROM (memory backup not required) |
| Memory cassette (Memory board) | FX1N-EEPROM-8L (8000 steps EEPROM: Only 2000 steps can be used in FX1S) |
| Writing function during running | Provided (Program can be modified while the PLC is running.) |
| Protection | Password protection provided (with entry code function) |
| Clock function | Built-in 1980 to 2079 (with correction for leap year), 2- or 4-digit year, accuracy 45 seconds/month at 25 °C *Precaution for clock function The current time of the built-in clock is backed up by a high-capacity capacitor (built-in). The large-capacity capacitor (built-in) fully charges in 30 minutes and retains the current value for ten days. |
| Basic instructions | ・Sequence instructions: 27 ・Step-ladder instructions: 2 |
| Applied instructions | Applied instructions: 85 kinds |
| Processing speed > Basic instructions | 0.55 to 0.7 μs/instruction |
| Processing speed > Applied instructions | 3.7 μs to several hundred μs/instruction |
| No. of input points | 6 points |
| No. of output points | 4 points |
| Total number of points | 30 points or less (in accordance with the I/O specification) Extension is impossible. |
| Input relay | X000 to X017 16 points (octal) Extension is impossible. (FX1S-10M□ is supported within the range of X000 to X005) |
| Output relay | Y000 to Y015 14 points (octal) Extension is impossible. (FX1S-10M□ is supported within the range of Y000 to Y003) |
| For general | M0 to M383 384 points |
| For keeping | M384 to M511 128 points *Precaution for keeping area The keeping area and non-keeping area are fixed. (Cannot be changed with parameter) The PLC power must be on for at least 5 minutes to accurately keep the data in the EEPROM. |
| For special | M8000 to M8255 256 points |
| Initial state | S0 to S9 10 points |
| Device > State > For keeping | All points held during power failure (S0 to S127) *Precaution for keeping area The keeping area and non-keeping area are fixed. (Cannot be changed with parameter) The PLC power must be on for at least 5 minutes to accurately keep the data in the EEPROM. |
| 100 ms | T0 to T62 63 points (0.1 to 3,276.7 sec) |
| 10 ms | When M8028 is turned ON, T32 to T62 (31 points) can be changed to a 10ms timer (0.01 to 327. 67 sec.) |
| 1 ms | T63 1 point (0.001 to 32.767 sec) |
| Others | Available as analog timers VR1: D8030, VR2: D8031 2 points (0 to 255) |
| 16 bits up | C0 to C15 16 points (Counting from 0 to 32,767) |
| 16 bits up (keeping) | C16 to C31 16 points (Counting from 0 to 32,767) (EEPROM keep) *Precaution for keeping area The keeping area and non-keeping area are fixed. (Cannot be changed with parameter) The PLC power must be on for at least 5 minutes to accurately keep the data in the EEPROM. |
| High-speed counter | [32 bits high-speed up/down (EEPROM keep)] C235 to C255 1-phase: 60 kHz, 10 kHz 2-phase: 30 kHz, 5 kHz The number of points that can be used and the input frequency are limited depending on the conditions of use. *Precaution for keeping area The keeping area and non-keeping area are fixed. (Cannot be changed with parameter) The PLC power must be on for at least 5 minutes to accurately keep the data in the EEPROM. |
| 16 bits for general | D0 to D127 128 points |
| 16 bits for keeping | D128 to D255 128 points (EEPROM keep) *Precaution for keeping area The keeping area and non-keeping area are fixed. (Cannot be changed with parameter) The PLC power must be on for at least 5 minutes to accurately keep the data in the EEPROM. |
| File register (keep) | D1000 to D2499 1500 points (Settable in file register in 500-point units.) (EEPROM) |
| 16 bits for special | D8000 to D8255 256 points |
| 16 bits for index | V0 to V7, Z0 to Z7: 16 points |
| For branching of JUMP and CALL | P0 to P63 64 points (For CJ instructions and CALL instructions, P63 jumps to END instruction) |
| Input interruption | I00□ to I50□: 6 points |
| Nesting | [For master control] N0 to N7: 8 points (For MC instructions) |
| Decimal number (K) | 16 bits: -32,768 to +32,767 32 bits: -2,147,483,648 to +2,147,483,647 |
| Hexadecimal number (H) | 16 bits: 0 to FFFF 32 bits: 0 to FFFFFFFF |
| Напряжение питания | 24 V DC |
| Напряжение питания | 24 V DC -15% to +10% |
| Frequency rating | - |
| Allowable instantaneous power failure time | Operation can be continued upon occurrence of instantaneous power failure for 5 ms or less. |
| Power fuse | 250 V 0.8 A |
| Rush current | 10 A max. 100 μs/24 V DC |
| Power consumption | 6 W Includes input current (7 or 5 mA per point). |
| 24 V DC service power supply | - |
| Input connection type | Terminal block (M3 screw) |
| Input type | Sink |
| Напряжение питания | 24 V DC ±10% |
| X000 to X007 | 3.3 kΩ |
| X010 or more | - |
| Input signal current > X000 to X007 | 7 mA/24 V DC |
| ON input sensitivity current > X000 to X007 | 4.5 mA or more |
| OFF input sensitivity current | 1.5 mA or less |
| Время отклика | Approx. 10 ms X000 to X017 (up to the main unit built-in number) have built-in digital filters, which can be changed to 0 to 15 ms in 1 ms increments using the application D8020. When 0 is specified, X000 and X001 are 10 μs, and X002 to X017 are 50 μs. (FX1S-10M□ is supported within the range of X000 to X005.) |
| Input signal form | No-voltage contact input NPN open collector transistor |
| Input circuit insulation | Photocoupler insulation |
| Indication of input operation | LED is lit when input is on |
| Output connection type | Terminal block (M3 screw) |
| Output type | Relay output |
| External power supply | 250 V AC 30 V DC or less |
| Resistance load | 2 A or less/1 output point 8 A or less/COM terminal |
| Inductive load | 80 VA |
| Min. load | 5 V DC, 2 mA (reference value) |
| Open circuit leakage current | - |
| Напряжение питания | - |
| OFF→ON | Approx. 10 ms |
| ON→OFF | Approx. 10 ms |
| Insulation of circuit | Mechanical insulation |
| Indication of output operation | When power is applied to relay coil, LED is lit. |
| 1-phase 1-count input | [C235, C236] Up to 2 points: Up to 60 kHz When used High-speed comparison SET/RESET: 30 kHz [C237 to C245] Up to 4 points: Up to 10 kHz When used High-speed comparison SET/RESET: 10 kHz The total frequency processed by the PLC with the high-speed counter and pulse density instruction (add double the input frequency when using a 2-phase counter) is a maximum of 60 kHz. When using the high-speed comparison SET/RESET, the total frequency processed by the PLC with the high-speed counter and pulse density instruction (add double the input frequency when using a 2-phase counter) is a maximum of 30 kHz. |
| 1-phase 2-count input | [C246] Up to 1 points: Up to 60 kHz When used High-speed comparison SET/RESET: 30 kHz [C247 to C250] Up to 2 points: Up to 10 kHz When used High-speed comparison SET/RESET: 10 kHz The total frequency processed by the PLC with the high-speed counter and pulse density instruction (add double the input frequency when using a 2-phase counter) is a maximum of 60 kHz. When using the high-speed comparison SET/RESET, the total frequency processed by the PLC with the high-speed counter and pulse density instruction (add double the input frequency when using a 2-phase counter) is a maximum of 30 kHz. |
| 2-phase 2-count input | [C251] Up to 1 point: Up to 30 kHz When used High-speed comparison SET/RESET: 15 kHz [C252 to C255] Up to 2 points: Up to 5 kHz When used High-speed comparison SET/RESET: 5 kHz The total frequency processed by the PLC with the high-speed counter and pulse density instruction (add double the input frequency when using a 2-phase counter) is a maximum of 60 kHz. When using the high-speed comparison SET/RESET, the total frequency processed by the PLC with the high-speed counter and pulse density instruction (add double the input frequency when using a 2-phase counter) is a maximum of 30 kHz. |
| Рабочая температура | 0 to 55°C (32 to 131 °F) when operating and -20 to 70°C (-4 to 158 °F) when stored |
| Ambient humidity | 35 to 85%RH (no condensation) when operating |
| Frequency: 10 to 57 Hz | Half amplitude: 0.035mm Sweep Count for X, Y, Z: 10 times (80 min in each direction) The criterion is shown in IEC61131-2. |
| Frequency: 57 to 150 Hz | Acceleration: 4.9 m/s 2 Sweep Count for X, Y, Z: 10 times (80 min in each direction) The criterion is shown in IEC61131-2. |
| Vibration resistance > Direct installing > Frequency: 10 to 57 Hz | Half amplitude: 0.075 mm Sweep Count for X, Y, Z: 10 times (80 min in each direction) The criterion is shown in IEC61131-2. |
| Vibration resistance > Direct installing > Frequency: 57 to 150 Hz | Acceleration: 9.8 m/s 2 Sweep Count for X, Y, Z: 10 times (80 min in each direction) The criterion is shown in IEC61131-2. |
| Shock resistance | 147 m/s 2 Acceleration, Action time: 11 ms, 3 times by half-sine pulse in each direction X, Y, and Z The criterion is shown in IEC61131-2. |
| Noise resistance | By noise simulator at noise voltage of 1,000 Vp-p, noise width of 1 μs, rise time of 1 ns and period of 30 to 100 Hz |
| Напряжение питания | Perform dielectric withstand voltage test at the following voltage between each terminals and the main unit ground terminal. Between power supply terminal (DC power supply) and ground terminal: 500 V AC for 1 min Between output terminal (relay) and ground terminal: 1.5 kV AC for 1 min |
| Insulation resistance | Perform insulation resistance test at the following voltage between each terminals and the main unit ground terminal. Between power supply terminal (DC power supply) and ground terminal: 5 MΩ or higher by 500 V DC insulation resistance tester Between output terminal (relay) and ground terminal: 5 MΩ or higher by 500 V DC insulation resistance tester |
| Grounding | Class D grounding (grounding resistance: 100 Ω or less) (Common grounding with a heavy electrical system is not allowed) Ground the PLC independently or jointly. |
| Working atmosphere | Free from corrosive or flammable gas and excessive conductive dusts |
| Working altitude | 2000 m or less The PLC cannot be used at a pressure higher than the atmospheric pressure to avoid damage. |
| Category (site listing) | Main unit |