FX2N-16MR-DS

Mitsubishi Electric Corporation (Factory Automation / FA Systems Group) FX2N-16MR-DS

FX2N-16MR-DS

Технические характеристики

Operation control systemStored-program repetitive operation method (dedicated LSI), with interrupt instructions
Input/output control systemBatch processing system (when END instruction is executed), Input/output refresh instruction and pulse catch function are provided.
Programming languageRelay symbol system + step-ladder system (SFC notation possible)
Max. memory capacity16000 steps 16000 steps including comments and file registers
Built-in memory capacity/type8000 steps RAM (backed up by built-in lithium battery)
Memory cassette (Memory board)・FX-RAM-8 (2000/4000/8000/16000 steps) ・FX-EPROM-8 (2000/4000/8000/16000 steps) ・FX-EEPROM-4 (2000/4000 steps) ・FX-EEPROM-8 (2000/4000/8000 steps) ・FX-EEPROM-16 (2000/4000/8000/16000 steps)
Expansion memory (Expansion memory board)FX2NC-ROM-E1 type function expansion memory board can be mounted on PLC version V3.00 and higher. ・Short mail send function ・Inverter operation control function ・16000 steps EEPROM (2000/4000/8000 steps also supported)
Writing function during runningProvided (Program can be modified while the PLC is running.)
ProtectionPassword protection provided (with entry code function)
Clock functionBuilt-in 1980 to 2079 (with correction for leap year) 2- or 4-digit year, accuracy within 45 seconds/month at 25 °C
Basic instructions・Sequence instructions: 27 ・Step-ladder instructions: 2
Applied instructionsApplied instructions: 132 kinds
Processing speed > Basic instructions0.08 μs/instruction
Processing speed > Applied instructions1.52 to several hundred μs/instruction
No. of input points8 points
No. of output points8 points
Remote I/O number of points (CC-Link)256 points or less including mounted I/O
Total number of points256 points or less (Extension combined number)
Input relayX000 to X267 184 points (octal) Extension combined number
Output relayY000 to Y267 184 points (octal) Extension combined number
For generalM0 to M499 500 points Battery-less backup area. Change to battery backup area by setting the parameters.
For keepingM500 to M1023 524 points Battery backup area. Change to battery-less backup area by setting the parameters.
For keeping (battery backup fixed area)M1024 to M3071 2048 points Battery backup fixed area. The area characteristics cannot be changed.
For specialM8000 to M8255 256 points
Initial stateS0 to S9 10 points
Device > State > For generalS10 to S499 490 points Battery-less backup area. Change to battery backup area by setting the parameters.
Device > State > For keepingS500 to S899 400 points Battery backup area. Change to battery-less backup area by setting the parameters.
For annunciatorS900 to S999 100 points Battery backup area. Change to battery-less backup area by setting the parameters.
100 msT0 to T199 200 points (0.1 to 3,276.7 sec)
10 msT200 to T245: 46 points (0.01 to 327.67 sec)
1 ms accumulating type (capacitor keep)T246 to T249: 4 points (0.001 to 32.767 sec) This retentive status is a battery backup fixed area. The area characteristics cannot be changed.
100 ms accumulating type (capacitor keep)T250 to T255: 6 points (0.1 to 3,276.7 sec) This retentive status is a battery backup fixed area. The area characteristics cannot be changed.
16 bits upC0 to C99 100 points (Counting from 0 to 32,767) Battery-less backup area. Change to battery backup area by setting the parameters.
16 bit increment (Battery backup)C100 to C199 100 points (Counting from 0 to 32,767) Battery backup area. Change to battery-less backup area by setting the parameters.
32 bit both directionsC200 to C219 20 points (Counting from -2,147,483,648 to +2,147,483,647) Battery-less backup area. Change to battery backup area by setting the parameters.
32 bit both directions (Battery backup)C220 to C234 15 points (Counting from -2,147,483,648 to +2,147,483,647) Battery backup area. Change to battery-less backup area by setting the parameters.
High-speed counter[32 bits high-speed up/down] Up to 6 points can be used between C235 and C255. 1-phase: 60 kHz, 10 kHz 2-phase: 30 kHz, 5 kHz The number of points that can be used and the input frequency are limited depending on the conditions of use. Battery backup area. Change to battery-less backup area by setting the parameters.
16 bits for generalD0 to D199 200 points Battery-less backup area. Change to battery backup area by setting the parameters.
16 bit for keeping (Battery backup)D200 to D511 312 points Battery backup area. Change to battery-less backup area by setting the parameters.
16 bit for keeping (Battery backup fixed area)D512 to D7999: 7488 points (D1000 and later can be set as file register points in 500-point units) This retentive status is a battery backup fixed area. The area characteristics cannot be changed.
16 bits for specialD8000 to D8255 256 points
16 bits for indexV0 to V7, Z0 to Z7: 16 points
For branching of JUMP and CALLP0 to P127 128 points (For CJ instructions and CALL instructions, P63 jumps to END instruction)
Input interruptionI00□ to I50□: 6 points
Timer interruptionI6□□ to I8□□: 3 points
Counter interruptionI010 to I060: 6 points (For HSCS instructions)
Nesting[For master control] N0 to N7: 8 points (For MC instructions)
Decimal number (K)16 bits: -32,768 to +32,767 32 bits: -2,147,483,648 to +2,147,483,647
Hexadecimal number (H)16 bits: 0 to FFFF 32 bits: 0 to FFFFFFFF
Напряжение питания24 V DC
Напряжение питания24 V DC -30%, +20%
Frequency rating-
Allowable instantaneous power failure timeOperation can be continued upon occurrence of instantaneous power failure for 5 ms or less.
Power fuse250 V 3 A
Rush current-
Power consumption20 W
24 V DC service power supply-
5 V DC built-in power supply290 mA
Input connection typeTerminal block (M3 screw)
Input typeSink/source
Напряжение питания24 V DC ±10% When using a DC power supply type, complies with the power voltage range of each unit.
X000 to X0073.3 kΩ
X010 or more-
Input signal current > X000 to X0077 mA/24 V DC
ON input sensitivity current > X000 to X0074.5 mA or more
OFF input sensitivity current1.5 mA or less
Время откликаApprox. 10 ms X000 to X017 (up to the main unit built-in number) have built-in digital filters, which can be changed to 0 to 60 ms in 1 ms increments using the application instructions or D8020. When 0 is specified, X000 and X001 are 20 μs, and X002 to X017 are 50μs. (FX2N-16N□ is supported within the range of X000 to X007.)
Input signal formNo-voltage contact input Sink: NPN open collector transistor Source: PNP open collector transistor
Input circuit insulationPhotocoupler insulation
Indication of input operationLED is lit when input is on
Output connection typeTerminal block (M3 screw)
Output typeRelay output
External power supply250 V AC 30 V DC or less
Resistance load1 output point/common terminal: 2 A or less 4 output points/common terminal: 8 A or less 8 output points/common terminal: 8 A or less
Inductive load80 VA
Min. load5 V DC, 2 mA (reference value)
Open circuit leakage current-
Напряжение питания-
OFF→ONApprox. 10 ms
ON→OFFApprox. 10 ms
Insulation of circuitMechanical insulation
Indication of output operationWhen power is applied to relay coil, LED is lit.
1-phase 1-count input[C235, C236] Up to 2 points: Up to 60 kHz When used High-speed comparison SET/RESET: 10 kHz When used High-speed zone compare HSZ: 5.5 kHz [C237 to C245] Up to 4 points: Up to 10 kHz When used High-speed comparison SET/RESET: 10 kHz When used High-speed zone compare HSZ: 5.5 kHz The total frequency processed by the PLC with the high-speed counter, pulse output instruction, and pulse density instructions (for 2-phase counters, add twice the input frequency) is a maximum of 20 kHz. When using the high-speed comparison SET/RESET, the total frequency processed by the PLC with the high-speed counter, pulse output instruction, and pulse density instruction (add double the input frequency when using a 2-phase counter) is a maximum of 11 kHz. The total frequency processed by the PLC with the high-speed counter, pulse output instruction, and pulse density instructions (for 2-phase counters, add twice the input frequency) is a maximum of 5.5 kHz.
1-phase 2-count input[C246] Up to 1 point: Up to 60 kHz When used High-speed comparison SET/RESET: 10 kHz When used High-speed zone compare HSZ: 5.5 kHz [C247 to C250] Up to 2 points: Up to 10 kHz When used High-speed comparison SET/RESET: 10 kHz When used High-speed zone compare HSZ: 5.5 kHz The total frequency processed by the PLC with the high-speed counter, pulse output instruction, and pulse density instructions (for 2-phase counters, add twice the input frequency) is a maximum of 20 kHz. When using the high-speed comparison SET/RESET, the total frequency processed by the PLC with the high-speed counter, pulse output instruction, and pulse density instruction (add double the input frequency when using a 2-phase counter) is a maximum of 11 kHz. The total frequency processed by the PLC with the high-speed counter, pulse output instruction, and pulse density instructions (for 2-phase counters, add twice the input frequency) is a maximum of 5.5 kHz.
2-phase 2-count input[C251] Up to 1 point: Up to 30 kHz When used High-speed comparison SET/RESET: 5 kHz When used High-speed zone compare HSZ: 4 kHz [C252 to C255] Up to 2 points: Up to 5 kHz When used High-speed comparison SET/RESET: 4 kHz When used High-speed zone compare HSZ: 4 kHz The total frequency processed by the PLC with the high-speed counter, pulse output instruction, and pulse density instructions (for 2-phase counters, add twice the input frequency) is a maximum of 20 kHz. When using the high-speed comparison SET/RESET, the total frequency processed by the PLC with the high-speed counter, pulse output instruction, and pulse density instruction (add double the input frequency when using a 2-phase counter) is a maximum of 11 kHz. The total frequency processed by the PLC with the high-speed counter, pulse output instruction, and pulse density instructions (for 2-phase counters, add twice the input frequency) is a maximum of 5.5 kHz.
Рабочая температура0 to 55°C (32 to 131°F) when operating and -20 to 70°C (-4 to 158°F) when stored
Ambient humidity35 to 85%RH (no condensation) when operating
Frequency: 10 to 57 HzHalf amplitude: 0.035mm Sweep Count for X, Y, Z: 10 times (80 min in each direction) The criterion is shown in IEC61131-2.
Frequency: 57 to 150 HzAcceleration: 4.9 m/s 2  Sweep Count for X, Y, Z: 10 times (80 min in each direction) The criterion is shown in IEC61131-2.
Vibration resistance > Direct installing > Frequency: 10 to 57 HzHalf amplitude: 0.075 mm Sweep Count for X, Y, Z: 10 times (80 min in each direction) The criterion is shown in IEC61131-2.
Vibration resistance > Direct installing > Frequency: 57 to 150 HzAcceleration: 9.8 m/s 2 Sweep Count for X, Y, Z: 10 times (80 min in each direction) The criterion is shown in IEC61131-2.
Shock resistance147 m/s 2 Acceleration, Action time: 11 ms, 3 times by half-sine pulse in each direction X, Y, and Z The criterion is shown in IEC61131-2.
Noise resistanceBy noise simulator at noise voltage of 1,000 Vp-p, noise width of 1 μs, rise time of 1 ns and period of 30 to 100 Hz
Напряжение питанияPerform dielectric withstand voltage test at the following voltage between each terminals and the main unit ground terminal. Between power supply terminal (DC power supply) and ground terminal: 500 V AC for 1 min Between output terminal (relay) and ground terminal: 1.5 kV AC for 1 min
Insulation resistancePerform insulation resistance test at the following voltage between each terminals and the main unit ground terminal. Between power supply terminal (DC power supply) and ground terminal: 5 MΩ or higher by 500 V DC insulation resistance tester Between output terminal (relay) and ground terminal: 5 MΩ or higher by 500 V DC insulation resistance tester
GroundingClass D grounding (grounding resistance: 100 Ω or less) (Common grounding with a heavy electrical system is not allowed) Ground the PLC independently or jointly.
Working atmosphereFree from corrosive or flammable gas and excessive conductive dusts
Working altitude2000 m or less Do not use the PLC under pressure higher than the atmospheric pressure. Doing so may damage the PLC.
Category (site listing)Main unit