Mitsubishi Electric Corporation (Factory Automation / FA Systems Group) FX2NC-16MT
FX2NC-16MT
Технические характеристики
| Operation control system | Stored-program repetitive operation method (dedicated LSI), with interrupt instructions |
|---|---|
| Input/output control system | Batch processing system (when END instruction is executed), Input/output refresh instruction and pulse catch function are provided. |
| Programming language | Sequence program |
| Max. memory capacity | 16000 steps 16000 steps including comments and file registers |
| Built-in memory capacity/type | 8000 steps RAM (backed up by built-in lithium battery) |
| Memory cassette (Memory board) | ・FX2NC-EEPROM-16 (2000/4000/8000/16000 steps) ・FX2NC-EEPROM-4C (2000/4000 steps with real time clock function) ・FX2NC-EEPROM-16C (2000/4000/8000/16000 steps with real time clock function) |
| Expansion memory (Expansion memory board) | FX2NC-ROM-CE1 type function expansion memory board can be mounted on PLC version V3.00 and higher. • Short mail send function • Inverter operation control function • 16000 steps with real time clock function EEPROM (2000/4000/8000 steps also supported) |
| Writing function during running | Provided (Program can be modified while the PLC is running.) |
| Protection | Password protection provided (with entry code function) |
| Clock function | Usable by mounting FX2NC-RTC, FX2NC-EEPROM-4C, FX2NC-EEPROM-16C, or FX2NC-ROM-CE1 1980 to 2079 (with correction for leap year) 2- or 4-digit year, accuracy within 45 seconds/month at 25°C |
| Basic instructions | ・Sequence instructions: 27 ・Step-ladder instructions: 2 |
| Applied instructions | Applied instructions: 132 kinds |
| Processing speed > Basic instructions | 0.08 μs/instruction |
| Processing speed > Applied instructions | 1.52 to several hundred μs/instruction |
| No. of input points | 8 points |
| No. of output points | 8 points |
| Remote I/O number of points (CC-Link) | 256 points or less including mounted I/O |
| Total number of points | 256 points or less (Extension combined number) |
| Input relay | X000 to X267 184 points (octal) Extension combined number |
| Output relay | Y000 to Y267 184 points (octal) Extension combined number |
| For general | M0 to M499 500 points Battery-less backup area. Change to battery backup area by setting the parameters. |
| For keeping | M500 to M1023 524 points Battery backup area. Change to battery-less backup area by setting the parameters. |
| For keeping (battery backup fixed area) | M1024 to M3071 2048 points Battery backup fixed area. The area characteristics cannot be changed. |
| For special | M8000 to M8255 256 points |
| Initial state | S0 to S9 10 points |
| Device > State > For general | S10 to S499 490 points Battery-less backup area. Change to battery backup area by setting the parameters. |
| Device > State > For keeping | S500 to S899 400 points Battery backup area. Change to battery-less backup area by setting the parameters. |
| For annunciator | S900 to S999 100 points Battery backup area. Change to battery-less backup area by setting the parameters. |
| 100 ms | T0 to T199 200 points (0.1 to 3,276.7 sec) |
| 10 ms | T200 to T245: 46 points (0.01 to 327.67 sec) |
| 1 ms accumulating type | T246 to T249: 4 points (0.001 to 32.767 sec) This retentive status is a battery backup fixed area. The area characteristics cannot be changed. |
| 100 ms accumulating type | T250 to T255: 6 points (0.1 to 3,276.7 sec) This retentive status is a battery backup fixed area. The area characteristics cannot be changed. |
| 16 bits up | C0 to C99 100 points (Counting from 0 to 32,767) Battery-less backup area. Change to battery backup area by setting the parameters. |
| 16 bit increment (Battery backup) | C100 to C199 100 points (Counting from 0 to 32,767) Battery backup area. Change to a battery-less backup area by setting the parameters. |
| 32 bits up or down | C200 to C219 20 points (Counting from -2,147,483,648 to +2,147,483,647) Battery-less backup area. Change to battery backup area by setting the parameters. |
| 32 bit up/down (Battery backup) | C220 to C234 15 points (Counting from -2,147,483,648 to +2,147,483,647) Battery backup area. Change to battery-less backup area by setting the parameters. |
| High-speed counter | [32 bits high-speed up/down] Up to 6 points can be used between C235 and C255. 1-phase: 60 kHz, 10 kHz 2-phase: 30 kHz, 5 kHz The number of points that can be used and the input frequency are limited depending on the conditions of use. Battery backup area. Change to battery-less backup area by setting the parameters. |
| 16 bits for general | D0 to D199 200 points Battery-less backup area. Change to battery backup area by setting the parameters. |
| 16 bit for keeping (Battery backup) | D200 to D511 312 points Battery backup area. Change to battery-less backup area by setting the parameters. |
| 16 bit for keeping (Battery backup fixed area) | D512 to D7999: 7488 points (D1000 and later can be set as file register points in 500-point units) This retentive status is a battery backup fixed area. The area characteristics cannot be changed. |
| 16 bits for special | D8000 to D8195 106 points |
| 16 bits for index | V0 to V7, Z0 to Z7: 16 points |
| For branching of JUMP and CALL | P0 to P127 128 points (For CJ instructions and CALL instructions, P63 jumps to END instruction) |
| Input interruption | I00□ to I50□: 6 points |
| Timer interruption | I6□□ to I8□□: 3 points |
| Counter interruption | I010 to I060: 6 points (For HSCS instructions) |
| Nesting | [For master control] N0 to N7: 8 points (For MC instructions) |
| Decimal number (K) | 16 bits: -32,768 to +32,767 32 bits: -2,147,483,648 to +2,147,483,647 |
| Hexadecimal number (H) | 16 bits: 0 to FFFF 32 bits: 0 to FFFFFFFF |
| Напряжение питания | 24 V DC |
| Напряжение питания | 24 V DC -15%, +20% Ripple Voltage (p-p) 5% or less Use it within the range of 24 V DC +10% -10% when connecting FX2NC-64ET. |
| Allowable instantaneous power failure time | Operation can be continued upon occurrence of instantaneous power failure for 5 ms or less. |
| Power fuse | 250 V 3.15 A (3 A) |
| Rush current | 30 A max.0.5 ms / 24 V DC |
| Power consumption | 6 W |
| 5 V DC built-in power supply | 600 mA The power supply is not for external use. The power supply capacity specified above is for the I/O extension blocks, special function blocks and special adapters. |
| Input connection type | Connector |
| Input type | Sink |
| Напряжение питания | 24 V DC -15%, +20% |
| X000 to X007 | 3.3 kΩ |
| X010 or more | - |
| Input signal current > X000 to X007 | 7 mA/24 V DC |
| ON input sensitivity current > X000 to X007 | 4.5 mA or more |
| OFF input sensitivity current | 1.5 mA or less |
| Время отклика | Approx. 10 ms X000 to X017 (up to the main unit built-in number) have built-in digital filters, which can be changed to 0 to 60 ms in 1 ms increments using the application instructions or D8020. When 0 is specified, X000 and X001 are 20 μs, and X002 to X017 are 50 μs. (FX2NC-16M□ is supported within the range of X000 to X007.) |
| Input signal form | No-voltage contact input NPN open collector transistor |
| Input circuit insulation | Photocoupler insulation |
| Indication of input operation | LED is lit when input is on |
| Output connection type | Connector |
| Output type | Transistor/sink output |
| External power supply | 5-30 V DC |
| Resistance load | 1 output point/common terminal: 0.1 A or less 8 output points/common terminal: 0.8 A or less (Y000 to Y003 are 0.3 A/1 output point.) |
| Inductive load | 2.4 W/24 V DC (Y000 to Y003 are 7.2 W/24 V DC.) |
| Min. load | - |
| Open circuit leakage current | 0.1 mA/30 V DC |
| Напряжение питания | 1.5 V |
| OFF→ON | Y000,Y001: 15 μs or less Y002 or more: 0.2 ms or less |
| ON→OFF | Y000,Y001: 30 μs or less Y002 or more: 0.2 ms or less |
| Insulation of circuit | Photocoupler insulation |
| Indication of output operation | LED on panel lights when photocoupler is driven. |
| 1-phase 1-count input | [C235, C236] Up to 2 points: Up to 60 kHz When used High-speed comparison SET/RESET: 10 kHz When used High-speed zone compare HSZ: 5.5 kHz [C237 to C245] Up to 4 points: Up to 10 kHz When used High-speed comparison SET/RESET: 10 kHz When used High-speed zone compare HSZ: 5.5 kHz The total frequency processed by the PLC with the high-speed counter, pulse output instruction, and pulse density instructions (for 2-phase counters, add twice the input frequency) is a maximum of 20 kHz. When using the high-speed comparison SET/RESET, the total frequency processed by the PLC with the high-speed counter, pulse output instruction, and pulse density instruction (add double the input frequency when using a 2-phase counter) is a maximum of 11 kHz. The total frequency processed by the PLC with the high-speed counter, pulse output instruction, and pulse density instructions (for 2-phase counters, add twice the input frequency) is a maximum of 5.5 kHz. |
| 1-phase 2-count input | [C246] Up to 1 point: Up to 60 kHz When used High-speed comparison SET/RESET: 10 kHz When used High-speed zone compare HSZ: 5.5 kHz [C247 to C250] Up to 2 points: Up to 10 kHz When used High-speed comparison SET/RESET: 10 kHz When used High-speed zone compare HSZ: 5.5 kHz The total frequency processed by the PLC with the high-speed counter, pulse output instruction, and pulse density instructions (for 2-phase counters, add twice the input frequency) is a maximum of 20 kHz. When using the high-speed comparison SET/RESET, the total frequency processed by the PLC with the high-speed counter, pulse output instruction, and pulse density instruction (add double the input frequency when using a 2-phase counter) is a maximum of 11 kHz. The total frequency processed by the PLC with the high-speed counter, pulse output instruction, and pulse density instructions (for 2-phase counters, add twice the input frequency) is a maximum of 5.5 kHz. |
| 2-phase 2-count input | [C251] Up to 1 point: Up to 30 kHz When used High-speed comparison SET/RESET: 5 kHz When used High-speed zone compare HSZ: 4 kHz [C252 to C255] Up to 2 points: Up to 5 kHz When used High-speed comparison SET/RESET: 4 kHz When used High-speed zone compare HSZ: 4 kHz The total frequency processed by the PLC with the high-speed counter, pulse output instruction, and pulse density instructions (for 2-phase counters, add twice the input frequency) is a maximum of 20 kHz. When using the high-speed comparison SET/RESET, the total frequency processed by the PLC with the high-speed counter, pulse output instruction, and pulse density instruction (add double the input frequency when using a 2-phase counter) is a maximum of 11 kHz. The total frequency processed by the PLC with the high-speed counter, pulse output instruction, and pulse density instructions (for 2-phase counters, add twice the input frequency) is a maximum of 5.5 kHz. |
| Number of control axes | 2 independent axes |
| Maximum frequency | 20 kHz |
| Compatible main units | Transistor output type main unit |
| Pulse output instruction | ・Pulse Y Output (PLSY) ・Acceleration/Deceleration Setup (PLSR) Pulse output form: Pulse train (The direction is controlled with the sequence.) |
| Positioning instruction | ・Reads out the current value of ABS ([D]ABS) Supported with V3.00 or later |
| Рабочая температура | 0 to 55°C (32 to 131°F) when operating and -20 to 70°C (-4 to 158°F) when stored |
| Ambient humidity | 35 to 85%RH (no condensation) when operating |
| Frequency: 10 to 57 Hz | Half amplitude: 0.035mm Sweep Count for X, Y, Z: 10 times (80 min in each direction) The criterion is shown in IEC61131-2. |
| Frequency: 57 to 150 Hz | 4.9 m/s 2 Sweep Count for X, Y, Z: 10 times (80 min in each direction) The criterion is shown in IEC61131-2. |
| Shock resistance | 147 m/s 2 Acceleration, Action time: 11 ms, 3 times by half-sine pulse in each direction X, Y, and Z The criterion is shown in IEC61131-2. |
| Noise resistance | By noise simulator at noise voltage of 1,000 Vp-p, noise width of 1 μs, rise time of 1 ns and period of 30 to 100 Hz |
| Напряжение питания | Perform dielectric withstand voltage test at the following voltage between each terminals and the main unit ground terminal. Between power supply terminal (DC power supply) and ground terminal: 500 V AC for 1 min Between input terminal (24 V DC) and ground terminal: 500 V AC for 1 min Between output terminal (transistor) and ground terminal: 500 V AC for 1 min |
| Insulation resistance | Perform insulation resistance test at the following voltage between each terminals and the main unit ground terminal. Between power supply terminal (DC power supply) and ground terminal: 5 MΩ or higher by 500 V DC insulation resistance tester Between input terminal (24 V DC) and ground terminal: 5 MΩ or higher by 500 V DC insulation resistance tester Between output terminal (transistor) and ground terminal: 5 MΩ or higher by 500 V DC insulation resistance tester |
| Grounding | Class D grounding (grounding resistance: 100 Ω or less) (Common grounding with a heavy electrical system is not allowed) Ground the PLC independently or jointly. |
| Working atmosphere | Free from corrosive or flammable gas and excessive conductive dusts |
| Working altitude | 2000 m or less Do not use the PLC under pressure higher than the atmospheric pressure. Doing so may damage the PLC. |
| Category (site listing) | Main unit |