FX3GC-32MT/DSS

Mitsubishi Electric Corporation (Factory Automation / FA Systems Group) FX3GC-32MT/DSS

FX3GC-32MT/DSS

Технические характеристики

Operation control systemStored program repetitive operation system with interruption function
Input/output control systemBatch processing system (when END instruction is executed), Input/output refresh instruction and pulse catch function are provided.
Programming languageSequence program
Max. memory capacity32000 steps 32000 steps including comments and file registers
Built-in memory capacity/type32000 steps EEPROM (memory backup not required)
Writing function during runningProvided (Program can be modified while the PLC is running.)
ProtectionWith keyword/Customer keyword function
Clock functionBuilt-in 1980 to 2079 (with correction for leap year), 2- or 4-digit year, accuracy within ±45 seconds/month at 25°C *Precaution for clock function The current time of the built-in clock is backed up by a high-capacity capacitor (built-in). The large-capacity capacitor (built-in) fully charges in 30 minutes and retains the current value for ten days. The optional battery can also be used to hold the time.
Basic instructions・Sequence instructions: 29 ・Step-ladder instructions: 2
Applied instructionsApplied instructions: 120 kinds
Processing speed > Basic instructionsStandard mode: 0.21 μs/instruction (if the capacity for programming is set to less than 16000 steps) Extension mode: 0.42 μs/instruction (if the capacity for programming is set to more than 16001 steps)
Processing speed > Applied instructionsStandard mode: 0.5 μs to several hundred μs/instruction (if the capacity for programming is set to less than 16000 steps) Extension mode: 1.2 μs to several hundred μs/instruction (if the capacity for programming is set to more than 16001 steps)
No. of input points16 points
No. of output points16 points
CC-Link(3) 128 points or less *The total number of remote I/O points in CC-Link and AnyWireASLINK must be 128 points or less.
AnyWireASLINK(3) 128 points or less *The total number of remote I/O points in CC-Link and AnyWireASLINK must be 128 points or less.
Total number of pointsTotal of (1)+(2)+(3): 256 points or less (Extension-combined)
Input relayX000 to X177 128 points (octal) Extension-combined
Output relayY000 to Y177 128 points (octal) Extension-combined
For generalM0 to M383 384 points
For keeping (EEPROM keep)M384 to M1535 1152 points *Precaution for keeping area The keeping area other than M1536 to M7679 and non-keeping area are fixed. (Cannot be changed with parameter)
For general-purpose (can be changed to keeping)M1536 to M7679 6144 points These devices can be changed to the keep (battery backup) type using a parameter when the optional battery is used.
For specialM8000 to M8511: 512 points
Initial state (EEPROM keep)S0 to S9 10 points
Device > State > For keeping (EEPROM keep)S10 to S999 990 points
Device > State > For generalS1000 to S4095 3096 points These devices can be changed to the keep (battery backup) type using a parameter when the optional battery is used.
100 msT0 to T191: 192 points (0.1 to 3,276.7 sec)
100 ms (for subroutine/interruption subroutine)T192 to T199: 8 points (0.1 to 3,276.7 sec)
10 msT200 to T245: 46 points (0.01 to 327.67 sec)
1 ms accumulating type (EEPROM keep)T246 to T249 4 points (0.001 to 32.767 sec) *Precaution for the retentive status The retentive status is fixed. (Cannot be changed with parameter)
100 ms accumulating type (EEPROM keep)T250 to T255 6 points (0.1 to 3,276.7 sec) *Precaution for the retentive status The retentive status is fixed. (Cannot be changed with parameter)
1 msT256 to T319 64 points (0.001 to 32.767 sec)
16 bits upC0 to C15 16 points (Counting from 0 to 32,767)
16 bits up (EEPROM keep)C16 to C199 184 points (Counting from 0 to 32,767) *Precaution for the retentive status The retentive status is fixed. (Cannot be changed with parameter)
32 bits up or downC200 to C219 20 points (Counting from -2,147,483,648 to +2,147,483,647)
32 bits up/down (EEPROM keep)C220 to C234 15 points (Counting from -2,147,483,648 to +2,147,483,647) *Precaution for the retentive status The retentive status is fixed. (Cannot be changed with parameter)
High-speed counter[32 bits high-speed up/down (EEPROM keep)] Up to 6 points can be used between C235 and C255. 1-phase: 60 kHz, 10 kHz 2-phase: 30 kHz, 5 kHz The number of points that can be used and the input frequency are limited depending on the conditions of use.
16 bits for generalD0 to D127 128 points
For 16 bits keep (EEPROM keep)D128 to D1099 972 points
For 16 bits general (can be changed to keeping)D1100 to D7999 6900 points These devices can be changed to the keep (battery backup) type using a parameter when the optional battery is used.
File register (EEPROM keep)D1000 to D7999 Maximum 7000 points (Can be set as file registers in units of 500 points from D1000 in the program area (EEPROM) using parameters.)
16 bits for specialD8000 to D8511: 512 points
16 bits for indexV0 to V7, Z0 to Z7: 16 points
Device > Extension register > For 16 bits general (can be changed to keeping)R0 to R23999 24000 points These devices can be changed to the keep (battery backup) type using a parameter when the optional battery is used.
16 bits (EEPROM keep)ER0 to ER23999 24000 points Stored in the EEPROM built-in the main unit
For branching of JUMP and CALLP0 to P2047 2048 points (For CJ instructions and CALL instructions, P63 jumps to END instruction)
Input interruptionI00□ to I50□: 6 points
Timer interruptionI6□□ to I8□□: 3 points
Nesting[For master control] I00□ to I50□ 6 points
Decimal number (K)16 bits: -32,768 to +32,767 32 bits: -2,147,483,648 to +2,147,483,647
Hexadecimal number (H)16 bits: 0 to FFFF 32 bits: 0 to FFFFFFFF
Real number (E)32 bits: -1.0 × 2 128 to -1.0 × 2 -126 , 0, 1.0 × 2 -126 to 1.0 × 2 128 Decimal-point and exponential notations are possible.
Напряжение питания24 V DC Use an external power supply of 24 V DC ±10% when connecting the FX2NC-64ET or FX2N-32CCL.
Напряжение питания20.4 V to 28.8 V DC
Allowable instantaneous power failure timeOperation can be continued upon occurrence of instantaneous power failure for 5 ms or less.
Power fuse125V 3.15 A
Rush current35 A max. 0.5 ms / 24 V DC
Power consumption8 W (Power consumption changes according to the system configuration.)
Input connection typeConnector
Input typeSink
Напряжение питания24 V DC +20% -15%
X000 to X0073.3 kΩ
X010 or more4.3 kΩ
Input signal current > X000 to X0077 mA/24 V DC
Input signal current > X010 or more5 mA/24 V DC
ON input sensitivity current > X000 to X0074.5 mA or more
ON input sensitivity current > X010 or more3.5 mA or more
OFF input sensitivity current1.5 mA or less
Время откликаApprox. 10 ms X000 to X007 have built-in digital filters, which can be changed to 0 to 15 ms in 1 ms increments using the application instructions or D8020. The following is applied when 0 is set. X000, X001, X003, X004: 10 μs X002, X005, X006, X007: 50 μs
Input signal formNo-voltage contact input Sink: NPN open collector transistor Source: PNP open collector transistor
Input circuit insulationPhotocoupler insulation
Indication of input operationWhen photocoupler is driven, LED on panel is lit.
Output connection typeConnector
Output typeTransistor/source output
External power supply5-30 V DC
Resistance load0.3 A/1 point (Y000, Y001) 0.1 A/1 point (Y002 to Y017) Make sure that the total load current of 8 resistance load points is 0.8 A or less. When the two COM1 terminals are connected outside the PLC, resistance load is 1.6 A or less.
Inductive load[Y000, Y001] 7.2 W/1 point (24 V DC) Make sure that the total load of 16 inductive load points is 38.4W/24 V DC or less. [Y002 to Y017] 2.4 W/1 point (24 V DC) Make sure that the total load of 16 inductive load points is 38.4W/24 V DC or less.
Open circuit leakage current0.1 mA or less/30 V DC
Напряжение питания1.5 V or less
OFF→ON[Y000, Y001] 5μs or less/10 mA or more (5-24 V DC) [Y002 to Y017] 0.2 ms or less/100 mA (24 V DC)
ON→OFF[Y000, Y001] 5μs or less/10 mA or more (5-24 V DC) [Y002 to Y017] 0.2 ms or less/100 mA (24 V DC)
Insulation of circuitPhotocoupler insulation
Indication of output operationLED on panel lights when photocoupler is driven.
1-phase 1-count input[C235, C236] 60 kHz [C237] 10 kHz [C238, C239] 60 kHz [C240] 10 kHz [C241] 60 kHz [C242 to C245] 10 kHz When using multiple high-speed counters, make sure that the sum of used frequency does not exceed the overall frequency.
1-phase 2-count input[C246, C248(OP)] 60 kHz [C247, C248] 10 kHz [C249, C250] 10 kHz When using multiple high-speed counters, make sure that the sum of used frequency does not exceed the overall frequency.
2-phase 2-count input[C251, C253(OP)] 30 kHz [C254(OP)] 5 kHz [C252, C253] 5 kHz [C254, C255] 5 kHz When using multiple high-speed counters, make sure that the sum of used frequency does not exceed the overall frequency.
Number of control axes2 independent axes
Maximum frequency100 kHz
Compatible main unitsTransistor output type main unit
Pulse output instruction・Pulse Y Output (PLSY) ・Acceleration/Deceleration Setup (PLSR) Pulse output form: Pulse train (The direction is controlled with the sequence.)
Positioning instruction・Reads out the current value of ABS ([D]ABS) ・zero return with DOG search function [DSZR] ・zero return [ZRN] (without DOG search function) Decelerates when near-point DOG is ON, Stops when near-point DOG is OFF. (This is different from the zero return operation by counting the zero point signal.) ・Variable speed Pulse Output [PLSV] ・Drive to Increment [DRVI] ・Drive to Absolute [DRVA] ・Positioning using batch setting method ([D]TBL) Pulse output form: "Pulse train + direction" method
Рабочая температура0 to 55°C (32 to 131°F) when operating and -25 to 75°C (-13 to 167°F) when stored
Ambient humidity5 to 95%RH (no condensation) when operating
Frequency: 10 to 57 HzHalf amplitude: 0.035mm Sweep Count for X, Y, Z: 10 times (80 min in each direction) The criterion is shown in IEC61131-2.
Frequency: 57 to 150 HzAcceleration: 4.9 m/s 2  Sweep Count for X, Y, Z: 10 times (80 min in each direction) The criterion is shown in IEC61131-2.
Shock resistance147 m/s 2 Acceleration, Action time: 11 ms, 3 times by half-sine pulse in each direction X, Y, and Z The criterion is shown in IEC61131-2.
Noise resistanceBy noise simulator at noise voltage of 1,000 Vp-p, noise width of 1 μs, rise time of 1 ns and period of 30 to 100 Hz
Напряжение питанияBetween batch of all terminals and ground terminal: 500 V AC for one minute
Insulation resistanceBetween batch of all terminals and ground terminal: 5 MΩ or higher by 500 V DC insulation resistance tester
GroundingClass D grounding (grounding resistance: 100 Ω or less) (Common grounding with a heavy electrical system is not allowed) Ground the PLC independently or jointly.
Working atmosphereFree from corrosive or flammable gas and excessive conductive dusts
Working altitude2000 m or less Do not use the PLC under pressure higher than the atmospheric pressure. Doing so may damage the PLC.
Category (site listing)Main unit