FX3S-14MR/ES

Mitsubishi Electric Corporation (Factory Automation / FA Systems Group) FX3S-14MR/ES

FX3S-14MR/ES

Технические характеристики

Operation control systemStored program repetitive operation system with interruption function
Input/output control systemBatch processing system (when END instruction is executed), Input/output refresh instruction and pulse catch function are provided.
Programming languageRelay symbol system + step-ladder system (SFC notation possible)
Max. memory capacity16000 steps, 16000 steps including comments and file registers
Built-in memory capacity/type16000 step EEPROM (memory backup not required)
Memory cassette (Option)FX3G-EEPROM-32L connectable (32000 steps EEPROM) FX3S series can use up to 16000 steps (program capacity is 4000 steps)
Writing function during runningProvided (Program can be modified while the PLC is running.)
ProtectionWith keyword/Customer keyword function
Clock functionBuilt-in 1980 to 2079 (with correction for leap year), 2- or 4-digit year, accuracy 45 seconds/month at 25 °C *Precaution for clock function The current time of the built-in clock is backed up by a high-capacity capacitor (built-in). The large-capacity capacitor (built-in) fully charges in 30 minutes and retains the current value for ten days.
Basic instructions・Sequence instructions: 29 ・Step-ladder instructions: 2
Applied instructionsApplied instructions: 116 kinds
Processing speed > Basic instructions0.21 μs/instruction
Processing speed > Applied instructions0.5 μs to several hundred μs/instruction
No. of input points8 points
No. of output points6 points
Total number of points30 points or less (Extension is impossible.)
Input relayX000 to X017 16 points (octal) Extension is impossible. (FX3S-14M□ is supported within the range X000 to X007)
Output relayY000 to Y015 14 points (octal) Extension is impossible. (FX3S-14M□ is supported within the range of Y000 to Y005)
For general 1M0 to M383 384 points
For keeping (EEPROM keep)M384 to M511 128 points *Precaution for keeping area The keeping area and non-keeping area are fixed. (Cannot be changed with parameter)
For general 2M512 to M1535 1024 points
For specialM8000 to M8511: 512 points
For initial state (EEPROM keep)S0 to S9 10 points *Precaution for keeping area The keeping area and non-keeping area are fixed. (Cannot be changed with parameter)
Device > State > For keeping (EEPROM keep)S10 to S127 118 points *Precaution for keeping area The keeping area and non-keeping area are fixed. (Cannot be changed with parameter)
For generalS128 to S255 128 points
100 msT0 to T31 63 points (0.1 to 3,276.7 sec)
100 ms/10 msT32 to T62 31 points (0.1 to 3,276.7 sec/0.01 to 327.67 sec) When M8028 is driven ON, timers T32 to T62 (31 points) are changed to 10 ms resolution.
1 msT63 to T127 65 points (0.001 to 32.767 sec)
1 ms accumulating typeT128 to T131 4 points (0.001 to 32.767 sec)
100 ms accumulating typeT132 to T137 6 points (0.1 to 3,276.7 sec)
OthersAvailable as analog timers VR1: D8030, VR2: D8031 2 points (0 to 255)
16 bits up (For general)C0 to C15 16 points (Counting from 0 to 32,767)
16 bits up (EEPROM keep)C16 to C31 16 points (Counting from 0 to 32,767) *Precaution for keeping area The keeping area and non-keeping area are fixed. (Cannot be changed with parameter)
32 bits up or downC200 to C234 35 points (Counting from -2,147,483,648 to +2,147,483,647)
High-speed counter[32 bits high-speed up/down (EEPROM keep)] Up to 6 points can be used between C235 and C255. 1-phase: 60 kHz, 10 kHz 2-phase: 30 kHz, 5 kHz The number of points that can be used and the input frequency are limited depending on the conditions of use. *Precaution for keeping area The keeping area and non-keeping area are fixed. (Cannot be changed with parameter)
16 bits for general 1D0 to D127 128 points
For 16 bits keep (EEPROM keep)D128 to D255 128 points *Precaution for keeping area The keeping area and non-keeping area are fixed. (Cannot be changed with parameter)
16 bits for general 2D256 to D2999 2744 points
File register (EEPROM keep)D1000 to D2999 2000 points (Settable in file register in 500-point units.)
16 bits for specialD8000 to D8511: 512 points
16 bits for indexV0 to V7, Z0 to Z7: 16 points
For branching of JUMP and CALLP0 to P255 256 points (For CJ instructions and CALL instructions, P63 jumps to END instruction)
Input interruptionI0□□ to I5□□ 6 points
Timer interruptionI6□□ to I8□□: 3 points
Nesting[For master control] N0 to N7: 8 points (For MC instructions)
Decimal number (K)16 bits: -32,768 to +32,767 32 bits: -2,147,483,648 to +2,147,483,647
Hexadecimal number (H)16 bits: 0 to FFFF 32 bits: 0 to FFFFFFFF
Real number (E)32 bits: -1.0 × 2 128 to -1.0 × 2 -126 , 0, 1.0 × 2 -126 to 1.0 × 2 128 Decimal-point and exponential notations are possible.
Напряжение питания100 to 240 V AC
Напряжение питания85 to 264 V AC
Frequency rating50/60 Hz
Allowable instantaneous power failure timeOperation can be continued upon occurrence of instantaneous power failure for 10 ms or less.
Power fuse250 V 1 A
Rush current15 A max. 5 ms or less/100 V AC, 28 A max. 5 ms or less/200 V AC
Power consumption19 W This item shows values when all 24 V DC service power supplies are used in the maximum configuration connectable to the main unit, and includes the input current (5 or 7 mA per point).
24 V DC service power supply400 mA
Input connection typeFixed terminal block (M3 screw)
Input typeSink/source
Напряжение питания24 V DC ±10%
X000 to X0073.3 kΩ
X010 or more-
Input signal current > X000 to X0077 mA/24 V DC
ON input sensitivity current > X000 to X0074.5 mA or more
OFF input sensitivity current1.5 mA or less
Время откликаApprox. 10 ms X000 to X017 have built-in digital filters, which can be changed to 0 to 15 ms in 1 ms increments using the application instructions or D8020. The following is applied when 0 is set. X000, X001: 10 μs X002 to X007: 50 μs X010 to X017: 200 μs
Input signal formNo-voltage contact input Sink: NPN open collector transistor Source: PNP open collector transistor
Input circuit insulationPhotocoupler insulation
Indication of input operationWhen photocoupler is driven, LED on panel is lit.
Output connection typeFixed terminal block (M3 screw)
Output typeRelay output
External power supply30 V DC or less, 240 V AC or less (250 V AC or less when the unit does not comply with CE, UL or cUL standards)
Resistance load2 A/1 point The total load current per common terminal should be the following value. 1 output point/common terminal: 2 A or less 4 output points/common terminal: 8 A or less
Inductive load80 VA (UL and cUL standards approved at 120 and 240 V AC.)
Min. load5 V DC, 2 mA (reference value)
Open circuit leakage current-
Напряжение питания-
OFF→ONApprox. 10 ms
ON→OFFApprox. 10 ms
Insulation of circuitMechanical insulation
Indication of output operationLED on panel lights when power is applied to relay coil.
1-phase 1-count input[C235, C236] 60 kHz [C237 to C240] 10 kHz [C241] 60 kHz [C242 to C245] 10 kHz When using multiple high-speed counters, make sure that the sum of used frequency does not exceed the overall frequency.
1-phase 2-count input[C246] 60 kHz [C248(OP)] 10 kHz [C247 to C250] 10 kHz When using multiple high-speed counters, make sure that the sum of used frequency does not exceed the overall frequency.
2-phase 2-count input[C251] 30 kHz [C253(OP), C252 to C255] 5 kHz When using multiple high-speed counters, make sure that the sum of used frequency does not exceed the overall frequency.
Рабочая температура0 to 55°C (32 to 131°F) when operating and -25 to 75°C (-13 to 167°F) when stored
Ambient humidity5 to 95%RH (no condensation) when operating
Frequency: 10 to 57 HzHalf amplitude: 0.035mm Sweep Count for X, Y, Z: 10 times (80 min in each direction) The criterion is shown in IEC61131-2.
Frequency: 57 to 150 HzAcceleration: 4.9 m/s 2  Sweep Count for X, Y, Z: 10 times (80 min in each direction) The criterion is shown in IEC61131-2.
Vibration resistance > Direct installing > Frequency: 10 to 57 HzHalf amplitude: 0.075 mm Sweep Count for X, Y, Z: 10 times (80 min in each direction) The criterion is shown in IEC61131-2.
Vibration resistance > Direct installing > Frequency: 57 to 150 HzAcceleration: 9.8 m/s 2 Sweep Count for X, Y, Z: 10 times (80 min in each direction) The criterion is shown in IEC61131-2.
Shock resistance147 m/s 2 Acceleration, Action time: 11 ms, 3 times by half-sine pulse in each direction X, Y, and Z The criterion is shown in IEC61131-2.
Noise resistanceBy noise simulator at noise voltage of 1,000 Vp-p, noise width of 1 μs, rise time of 1 ns and period of 30 to 100 Hz
Напряжение питанияPerform dielectric withstand voltage test at the following voltage between each terminals and the main unit ground terminal. Between power supply terminal (AC power supply) and ground terminal: 1.5 kV AC for 1 min Between 24 V DC service power supply connected to input terminal (24 V DC) and ground terminal: 500 V AC for 1 min Between output terminal (relay) and ground terminal: 1.5 kV AC for 1 min
Insulation resistancePerform insulation resistance test at the following voltage between each terminals and the main unit ground terminal. Between power supply terminal (AC power supply) and ground terminal: 5 MΩ or higher by 500 V DC insulation resistance tester Between 24 V DC service power supply connected to input terminal (24 V DC) and ground terminal: 5 MΩ or higher by 500 V DC insulation resistance tester Between output terminal (relay) and ground terminal: 5 MΩ or higher by 500 V DC insulation resistance tester
GroundingClass D grounding (grounding resistance: 100 Ω or less) (Common grounding with a heavy electrical system is not allowed) Ground the PLC independently or jointly.
Working atmosphereFree from corrosive or flammable gas and excessive conductive dusts
Working altitude2000 m or less The PLC cannot be used at a pressure higher than the atmospheric pressure to avoid damage.
Category (site listing)Main unit